Introduction to STS2/PDU Operations

8.2.2Transfer

Should the preferred source fail or be outside acceptable voltage limits, the STS2/PDU transfers the input to the alternate source until the problem is rectified in the preferred source. The unit can be set to automatically transfer the input back to the preferred source or allow the transfer to be done only manually.

8.2.3Transfer Inhibit

For a transfer to be completed between input sources, the sources must meet certain parameters or the transfer cannot take place. Uninterrupted transfer between sources is inhibited due to input source failure, sources out of sync, switch failure or the unit is in bypass mode.

8.2.4Bypass

The Static Transfer Switch 2 Power Distribution Unit can be manually bypassed to allow the power from a source to directly flow to the output load. This bypass allows the unit’s electronics to be ser- viced without dangerous voltages being present.

The STS2/PDU includes key-interlocked maintenance bypass breakers that allow either input source’s electronics to be bypassed for maintenance without interruption of power to the load. The maintenance bypass allows all electronics to be isolated from the input, output and bypass connec- tions. Bypass instructions are available from the touch screen and are discussed later in this manual.

8.3Operator Controls

The STS2/PDU is equipped with an interface to configure and monitor the unit either locally or remotely. The Color Graphical Display is a touch screen LCD that provides a color diagram (Mimic) that displays the current status of the unit. System parameters are displayed and help is available to define events. See Figure 58 below and Figure 57 in 7.0 - Installation Drawings. The touch screen menus allow the operator to initiate source transfers, view event and history logs and view bypass and other operational instructions.

Figure 58 STS2/PDU touch screen display

Mimic

Event controls

Event display

Display panel and help screen

Menu options

Touch screen control buttons allow you to reset alarms, silence the audible alarm, review configura- tions, event and history logs, preferred source, startup and bypass procedures and the help menu.

Qualified personnel, with a password, can use these menus to configure parameters, select a pre- ferred source and do manual source transfers.

Units can be accessed from a terminal or a PC running terminal emulation software attached to the unit. Through the RS-232 access, you can monitor and configure the unit, plus remotely select a pre- ferred source. See 12.1 - Using the RS-232 Port for instructions on using the RS-232 interface.

71

Page 79
Image 79
Liebert STS2, PDUTM manual Operator Controls, Transfer Inhibit, Bypass