INFORMATION
For the relationship between the warning display and
CALL OUT signal output, see page 81. The warning display of the item written “Fixed” in the CALL OUT output column displays unconditionally. For the item written “Selectable” in the CALL OUT output column, you can set the condition that CALL OUT signal is output. For example, the buzzer can be set to sound when reaching a value set in “HDD MAIN REMAIN” or “HDD SUB REMAIN” of the <CALL OUT SETTINGS> screen when “BUZZER” in the <REAR TERMINAL SETTINGS> screen is set to “WARNING.”
• HDD MAIN FULL/HDD SUB FULL
When the recordable HDD capacity becomes empty, a signal is output from the MODE OUT terminal which is set to “CALL OUT” in <REAR TERMINAL SETTINGS> screen and a “REC/FULL” appears on the screen for MAIN HDD. (For SUB HDD, “REC/SUB FULL” appears.)
Setting (default: “OFF”)
“ON”: Outputs a signal when the recording capacity becomes empty.
“OFF”: Does not output a signal when the recording capacity becomes empty.
1.Press the SET UP button } <SETTINGS> } <INITIAL SET UP/INFORMATION> } <REAR TERMINAL SETTINGS> } Select “HDD MAIN FULL” or “HDD SUB FULL” in the <CALL OUT SETTINGS> screen. Display the desired setting and determine such setting.
2.Press the CLEAR button or the SET UP button.
♦EMERGENCY REC DURATION
This item is used to set the recording time for emergency recording.
|
|
|
|
|
|
<REAR | TERMINAL SETTINGS> | OFF | |||
MODE | OUT | 1 |
| ||
MODE | OUT | 2 |
| OFF | |
MODE | OUT | 3 |
| OFF | |
MODE | OUT | 4 |
| OFF | |
MODE | OUT | 5 |
| OFF | |
KEY SOUND |
|
| ON | ||
BUZZER |
|
| OFF | ||
REMAIN HDD | |||||
CALL OUT SETTINGS |
| 10M | |||
>>EMERGENCY REC DURATION | |||||
|
|
|
|
|
|
For the details concerning EMERGENCY
RECORDING settings, see page 61.
Setting (default: “10M”)
“1M,” “2M,” “5M,” “10M,” “20M,” “30M,” “60M”
1.Press the SET UP button } <SETTINGS> } <INITIAL SET UP/INFORMATION> } Select “EMERGENCY REC DURATION” in the <REAR TERMINAL SETTINGS> screen. Display the desired setting and determine such setting.
2.Press the CLEAR button or the SET UP button.
■COMMUNICATION PORT SETTINGS
<COMMUNICATION PORT SETTINGS>
ETHERNET
♦
This menu is used to set the communication device connected to the
• MODE
This item is used to remotely control this unit via a PC connected to the
>>MODEREMOTE A
SETTINGS
Setting (default: “REMOTE A”)
“REMOTE A”: Controls this unit via a PC and this unit returns all the state information.
“REMOTE B”: Controls this unit via a PC and this unit returns only the state transition information.
“REMOTE C”: Controls this unit via a PC and this unit returns nothing.
“OFF”: Does not control this unit via a PC.
1.Press the SET UP button } <SETTINGS> } <INITIAL SET UP/INFORMATION> } Select “MODE” in the
2.Press the CLEAR button or the SET UP button.
•
This menu is used to set the
9600 | |
>>TRANSMISSION MODE | |
DATA BIT LENGTH | 8BIT |
PARITY BIT | NONE |
STOP BIT LENGTH | 1BIT |
DELIMITER | CR |
Set all the settings to the same values as the controlling PC.
ENGLISH