Chassis Connections

Connecting Power to the Chassis

Step

Action

 

 

5Place the grounding connectors over the posts, then secure the connectors using a 11/32-inch nut driver to tighten the #8 locking nuts to 15 in-lb.

 

4

Console

5

 

6

11/32-inch nutdriver

 

OR

Turn clockwise

Ground cable

to tighten nuts

to 15 in-lb.

to facility

 

ground.

CVX-0224A

6Ensure that the other end of the ground cable is properly connected for frame grounding.

Using the Compression Terminal

Note: In addition to the grounding location shown in the following section, the AC chassis option also contains an identical grounding location in the upper right corner of the rear of the chassis. Either location may be used.

To ground the CVX 600 chassis using the compression terminal, follow these steps:

Step

Action

 

 

1Locate a suitable ground cable at your facility.

2On the back of the chassis, locate the posts with the ground symbol.