Cabling and connections

6.1.2Installation instructions

1

Before starting the installation, check that none of the components of the

frequency converter are live.

 

2

If the frequency converter is installed outside either a switchgear,

separate cubicle or electrical room, it must be equipped with a protection

 

 

cover (see e.g. Figure 6-4) as provided by the regulations for IP21

 

protection class. For installations in a switchgear, separate cubicle or

 

electrical room, the cable protection plate is normally not necessary.

3

 

Place the motor cables sufficiently far from other cables:

 

! Avoid placing the motor cables in long parallel lines with other

 

 

 

 

cables

 

 

 

 

! If the motor cables runs in parallel with other cables, note the

 

 

minimum distances between the motor cables and other cables

 

 

given in the table below.

 

 

 

 

! The given distances also apply between the motor cables and

 

 

signal cables of other systems.

 

 

! The maximum length of the motor cables is 300 m (level H,

 

 

units with power greater than 1.5 kW) and 100 m (units with power

 

 

from 0.75 to 1.5 kW).

 

 

 

 

! The motor cables should cross other cables at an angle of 90

 

 

degrees.

 

 

 

 

 

 

 

 

 

 

 

Distance

Shielded

 

 

 

 

between cables

cable

 

 

 

 

[m]

[m]

 

 

 

 

0.3

50

 

 

 

 

1.0

200

 

 

 

 

 

 

 

4

If cable insulation checks are needed, see Chapter 6.1.4.

 