6.2.2Control terminal signals

 

 

 

 

 

 

 

 

 

 

 

Terminal

Signal

Technical information

 

 

1

 

+10 Vref

Reference voltage

Maximum current 10 mA

 

 

 

 

 

 

 

 

 

 

 

2

 

AI1+

Analogue input,

Selection V or mA with jumper block X1 (see page 45):

 

 

 

 

 

voltage or current

Default: 0– +10V (Ri = 200 k

)

 

 

 

 

 

 

 

(-10V…..+10V Joy-stick control, selected with a jumper)

 

 

 

 

 

 

0– 20mA (Ri = 250

)

 

 

 

3

 

GND/AI1–

Analogue input common

Differential input if not connected to ground;

 

 

 

 

 

 

Allows ± 20V differential mode voltage to GND

 

 

4

 

AI2+

Analogue input,

Selection V or mA with jumper block X2 (see page 45):

 

 

 

 

 

voltage or current

Default: 0– 20mA (Ri = 250

)

 

 

 

 

 

 

0– +10V (Ri = 200 k

)

 

 

 

 

 

 

(-10V…..+10V Joy-stick control, selected with a jumper)

 

 

5

 

GND/AI2–

Analogue input common

Differential input if not connected to ground;

 

 

 

 

 

 

Allows ± 20V differential mode voltage to GND

 

 

6

 

24 Vout

24V auxiliary voltage

± 15%, maximum current 250mA (all boards total);150mA

 

 

 

 

(bidirectional)

 

(from single board); Can also be used as external power

 

 

 

 

 

 

backup for the control unit (and fieldbus)

 

 

7

 

GND

I/O ground

Ground for reference and controls

 

 

 

 

 

 

 

 

 

 

 

8

 

DIN1

Digital input 1

Ri = min. 5k

 

 

 

 

9

 

DIN2

Digital input 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

DIN3

Digital input 3

 

 

 

 

 

 

 

 

 

 

 

 

11

 

CMA

Digital input common A for

Must be connected to GND or 24V of I/O terminal or

 

 

 

 

 

DIN1, DIN2 and DIN3.

to external 24V or GND

 

 

 

 

 

 

 

 

Selection with jumper block X3 (see page 45):

 

 

12

 

24 Vout

24V auxiliary voltage

Same as terminal #6

 

 

 

 

 

 

(bidirectional)

 

 

 

 

 

 

13

 

GND

I/O ground

Same as terminal #7

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

DIB4

Digital input 4

 

 

 

 

 

 

Ri = min. 5k

 

 

 

 

15

 

DIB5

Digital input 5

 

 

 

 

 

16

 

DIB6

Digital input 6

 

 

 

 

 

17

 

CMB

Digital input common B for

Must be connected to GND or 24V of I/O terminal or

 

 

 

 

 

DIB4, DIB5 and DIB6

to external 24V or GND

 

 

 

 

 

 

 

 

Selection with jumper block X3 (see page 45):

 

 

18

 

AO1+

Analogue signal (+output)

Output signal range:

 

 

 

 

 

 

 

 

Current 0(4)–20mA, RL max 500or

 

 

19

 

AO1–

Analogue output common

 

 

 

 

 

 

Voltage 0—10V, R L >1k

 

 

 

 

 

 

 

 

Selection with jumper block X6 (see page 45):

 

 

20

 

DO1

Open collector output

Maximum Uin = 48VDC

 

 

 

 

 

 

 

 

Maximum current = 50 mA

 

 

 

 

 

 

NXOPTA3

 

 

 

 

 

 

21

 

RO1/1

Relay output 1

Maximum switching voltage 250VAC, 125VDC

 

 

 

 

 

 

Maximum switching current8A/24VDC,

 

 

22

 

RO1/2

 

 

 

 

 

 

 

 

0.4A/250VDC

 

 

23

 

RO1/3

 

 

 

 

 

 

Min. switching load

5V/10mA

 

 

 

 

 

 

 

 

25

 

 

Relay output 2

Maximum switching voltage 250VAC, 125VDC

 

 

 

RO2/1

 

Maximum switching current8A/24VDC, 0.4A/250VDC

 

 

26

 

RO2/2

 

Min. switching load

5V/10mA

 

 

28

 

TI1/1

Thermistor input 1

Basic galvanic isolation

 

 

 

 

29

 

TI1/2

 

Double isolation when connected to thermistor

 

 

 

 

 

 

 

 

 

 

Table 6-5. Control I/O terminal signals