Technical data

17(86)

4.3 Technical data

 

 

 

 

 

 

 

 

 

 

 

Mains

Input voltage Uin

208...240 V; 380...500 V; 525...690 V; -15%...+10%

 

 

 

connection

Input frequency

45...66 Hz

 

 

 

 

Connection to mains

Once per minute or less (normal case)

 

 

 

Motor

Output voltage

0—U in

 

 

 

connection

Continuous output current

IH: Ambient temperature max. +50ºC,

 

 

 

 

 

overload 1.5 x IH (1min/10min)

 

 

 

 

 

IL: Ambient temperature max. +40ºC,

 

 

 

 

 

overload 1.1 x IL (1min/10min)

 

 

 

 

 

 

 

 

 

 

Starting torque

150% (Low overload); 200% (High overload)

 

 

 

 

Starting current

2.5 x IH 2 secs every 20 secs, if output frequency <30Hz

 

 

 

 

 

and temperature of heatsink <+60ºC (up to 400 kW)

 

 

 

 

 

 

 

 

 

 

Output frequency

0...320 Hz (NXS); 7200 Hz (Special)

 

 

 

 

Frequency resolution

0.01 Hz (NXS); Application dependent (NXP)

 

 

 

Control

Control method

Frequency Control U/f

 

 

 

characteristrics

 

Open Loop Sensorless Vector Control

 

 

 

 

 

Closed Loop Frequency Control

 

 

 

 

 

Closed Loop Vector Control (NXP only)

 

 

 

 

 

 

 

 

 

 

Switching frequency

Up to and including NX 0061:

 

 

 

 

(See parameter 2.6.9)

1...16 kHz; Factory default 10 kHz

 

 

 

 

 

From NX 0072:

 

 

 

 

 

1...10 kHz; Factory default 3.6 kHz

 

 

 

 

 

 

 

 

 

 

Frequency reference

 

 

 

 

 

Analogue input

Resolution 0.1% (10bit), accuracy ±1%

 

 

 

 

Panel reference

Resolution 0.01 Hz

 

 

 

 

Field weakening point

30...320 Hz

 

 

 

 

Acceleration time

0...3000 sec

 

 

 

 

Deceleration time

0...3000 sec

 

 

 

 

Braking torque

DC-brake: 30%*TN (without brake option)

 

 

 

Ambient

Ambient operating

–10ºC (no frost)... +50ºC: I H

 

 

 

conditions

temperature

–10ºC (no frost)... +40ºC: I L

 

 

 

 

Storage temperature

–40ºC...+70ºC

 

 

 

 

Relative humidity

0 to 95% RH, non-condensing, non-corrosive,

 

 

 

 

 

no dripping water

 

 

 

 

Air quality:

 

 

 

 

 

- chemical vapours

IEC 721-3-3, unit in operation, class 3C2

 

 

 

 

- mechanical particles

IEC 721-3-3, unit in operation, class 3S2

 

 

 

 

Altitude

100% load capacity (no derating) up to 1000m

 

 

 

 

 

1-% derating for each 100m above 1000m; max. 3000m

 

 

 

 

 

 

 

 

 

 

Vibration

5...200 Hz

 

 

 

 

(IEC 721-3-3, EN50178/

Displacement amplitude 3 mm at 5...10.7 Hz

 

 

 

 

EN60068-2-6, IEC68-2-6

Max acceleration amplitude 0.7 G at 10.7...200 Hz

 

 

 

 

(68-2-34, -35, -36)

 

 

 

 

 

 

 

 

 

 

 

Shock

UPS Drop Test (for applicable UPS weights)

 

 

 

 

EN50178, IEC 68-2-27

Storage and shipping: max 15 G, 11 ms (in package)

 

 

 

 

Enclosure class

IP21/NEMA1 standard in entire kW/HP range

 

 

 

 

 

IP54/NEMA12 option in entire kW/HP range

 

 

 

 

 

Note! Keypad installation required for IP54

 

 

 

 

 

 

 

 

Table 4-2. Technical data (continues on next page)