7

Control keypad

61(86)

Fault code

Fault

Possible cause

Correcting measures

 

16

Motor

Motor overheating has been detected by

Decrease the motor load.

 

 

overtemperature

frequency converter motor temperature

If no motor overload exists, check the

 

 

 

model. Motor is overloaded.

temperature model parameters.

 

17

Motor underload

Motor underload protection has tripped.

 

 

 

22

EEPROM

Parameter save fault

 

 

 

23

checksum fault

faulty operation

 

 

 

 

 

component failure

 

 

 

24

Changed data

Changes may have occurred in the

No special actions required. Take a

 

 

warning

different counter data due to mains

critical attitude to the counter data.

 

 

 

interruption

 

 

 

25

Microprocessor

faulty operation

Reset the fault

and restart.

 

 

watchdog fault

component failure

 

 

Should the fault re-occur, contact your

 

 

 

 

 

nearest distributor..

 

 

32

Fan cooling

Cooling fan of the frequency converter

Contact your nearest distributor..

 

 

 

does not start, when ON command is

 

 

 

 

 

given

 

 

 

34

CAN bus

Sent message not acknowledged.

Ensure that there is another device on

 

 

communication

 

 

the bus with the same configuration.

 

36

Control unit

NXS Control Unit can not control NXP

Change control units

 

 

 

 

Power Unit and vice versa

 

 

 

37

Device change

Option board changed.

Reset

 

 

 

 

Different power rating of drive.

 

 

 

38

Device added

Option board added.

Reset

 

 

 

 

Drive of different power rating added.

 

 

 

39

Device removed

Option board removed.

Reset

 

 

 

 

Drive removed.

 

 

 

40

Device unknown

Unknown option board or drive.

 

 

 

41

IGBT temperature

IGBT Inverter Bridge overtemperature

Check loading.

 

 

 

 

protection has detected too high a short

Check motor size.

 

 

 

 

term overload current

 

 

 

42

Brake resistor

Brake resistor overtemperature protection

Set the deceleration time longer.

 

 

overtemperature

has detected too heavy braking

Use external brake resistor.

 

43

Encoder fault

Note the exceptional Fault data record.

Check encoder channel connections.

 

 

 

See 7.3.4.3. Additional codes:

Check the encoder board.

 

 

 

1 = Encoder 1 channel A is missing

 

 

 

 

 

2 = Encoder 1 channel B is missing

 

 

 

 

 

3 = Both encoder 1 channels are missing

 

 

 

 

 

4 = Encoder reversed

 

 

 

50

Analogue input

Current at the analogue input is < 4mA.

Check the current loop circuitry.

 

 

Iin < 4mA

control cable is broken or loose

 

 

 

 

(selected signal

signal source has failed

 

 

 

 

range 4 to 20

 

 

 

 

 

 

mA)

 

 

 

 

 

51

External fault

Digital input fault.

 

 

 

52

Keypad

The connection between the control

Check keypad connection and possible

 

 

communication

keypad and the frequency converter is

keypad cable.

 

 

 

fault

broken.

 

 

Table 7-3. Fault codes

Page 61
Image 61
Nx Networks NX series user manual 6186, Fault code Possible cause Correcting measures