Fault tracing

9.FAULT TRACING

When a fault is detected by the frequency converter control electronics, the drive is stopped and the symbol F together with the ordinal number of the fault, the fault code and a short fault description appear on the display. The fault can be reset with the Reset button on the control keypad or via the I/O terminal. The faults are stored in the Fault history menu (M5) which can be browsed. The different fault codes can be found in the table below.

The fault codes, their causes and correcting actions are presented in the table below. The shadowed faults are A faults only. The faults written in white on black background may appear as both A and F fault.

 

 

 

 

 

 

 

 

 

 

 

Fault

Fault

 

Possible cause

Correcting measures

 

 

code

 

 

 

 

 

 

 

 

 

1

Overcurrent

Frequency converter has detected too

Check loading.

 

 

 

 

 

 

high a current (>4*In) in the motor cable:

Check motor size.

 

 

 

 

 

 

sudden heavy load increase

Check cables.

 

 

 

 

 

 

short circuit in motor cables

 

 

 

 

 

 

 

 

unsuitable motor

 

 

 

 

 

 

2

Overvoltage

The DC-link voltage has exceeded the

Make the deceleration time longer.

 

 

 

 

limits defined in Table 4-1.

 

 

 

 

 

 

 

 

too short a deceleration time

 

 

 

 

 

 

 

 

high overvoltage spikes in utility

 

 

 

 

 

 

3

Earth fault

Current measurement has detected that

Check motor cables and motor.

 

 

 

 

the sum of motor phase current is not

 

 

 

 

 

 

 

 

zero.

 

 

 

 

 

 

 

 

insulation failure in cables or motor

 

 

 

 

 

 

5

Charging switch

The

charging switch is open, when the

Reset the fault

and restart.

 

 

 

 

START command has been given.

 

 

 

 

Should the fault re-occur, contact your

 

 

 

 

faulty operation

 

 

 

 

nearest distributor.

 

 

 

 

 

 

component failure

 

 

 

 

 

 

 

 

 

 

 

 

6

Emergency

Stop signal has been given from the

 

 

 

 

 

 

 

stop

option board.

 

 

 

 

 

 

7

Saturation trip

Very high overload

Cannot be reset from the keypad.

 

 

 

 

Defective component

Switch off power. If this does not help

 

 

 

 

 

 

contact your nearest distributor.

 

 

8

System fault

The

frequency converter troubleshooting

Reset the fault

and restart.

 

 

 

 

system is unable to locate the fault.

 

 

 

 

Should the fault re-occur, contact your

 

 

 

 

 

 

 

 

 

 

 

 

nearest distributor,

 

 

 

 

9

Undervoltage

DC-link voltage is under the voltage limits

In case of temporary supply voltage

 

 

 

 

defined in.

break reset the fault

 

 

and restart

 

 

 

 

most probable cause: too low a

 

 

 

 

 

 

the frequency converter. Check the

 

 

 

 

 

supply voltage

 

 

 

 

supply voltage. If it is adequate, an

 

 

 

 

frequency converter internal fault

 

 

 

 

internal failure has occurred.

 

 

 

 

 

 

Contact your nearest distributor..

 

 

10

Input line

Input line phase is missing.

Check supply voltage and cable.

 

 

 

supervision

 

 

 

 

 

 

 

 

11

Output phase

Current measurement has detected that

Check motor cable and motor.

 

 

 

supervision

there is no current in one motor phase.

 

 

 

 

 

 

12

Brake chopper

no brake resistor installed

Check brake resistor.

 

 

 

 

 

supervision

brake resistor is broken

If the resistor is ok, the chopper is faulty.

 

 

 

 

brake chopper failure

Contactyour nearest distributor.

 

 

13

Frequency

Heatsink temperature is under –10°C

 

 

 

 

 

 

 

converter

 

 

 

 

 

 

 

 

 

under-

 

 

 

 

 

 

 

 

 

temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 