Cabling and connections

6.2.1.1Control cables

The control cables shall be at least 0.5 mm2 screened multicore cables, see Table 6-1. The maximum terminal wire size is 2.5 mm2 for the relay terminals and 1.5 mm2 for other terminals.

6.2.1.2Galvanic isolation barriers

The control connections are isolated from the mains potential and the GND terminals are permanently connected to ground. See Figure 6-17.

The digital inputs are galvanically isolated from the I/O ground. The relay outputs are additionally double-isolated from each other at 300VAC (EN-50178).

10Vref

 

 

Gate drivers

L1

L2

L3

GND

 

 

 

 

 

 

+24V

 

 

 

 

 

 

GND

Control I/O

 

 

 

 

 

AI1

ground

 

 

 

 

 

 

 

 

 

 

 

AI2+

 

 

 

 

 

 

AI2 -

 

Control

 

 

 

 

DIN1...

 

Main

 

 

 

Digital input

panel

 

 

 

DIN3

circuits

Control

 

group A

 

 

CMA

 

 

board

 

 

 

 

 

DIN4...

Digital input

 

 

 

 

 

DIN6

 

 

 

 

 

group B

 

 

 

 

 

CMB

Control

 

 

 

 

 

 

 

 

 

AO1+

Analogue

board

 

 

 

 

AO2 -

output

 

 

 

 

 

DO1

Digital

 

 

 

 

 

output

 

 

 

 

 

 

 

 

 

 

 

RO1/1

 

 

 

 

 

 

RO1/2

 

 

 

 

 

 

RO1/3

 

 

 

 

 

 

RO2/1

 

 

 

 

 

 

RO2/2

 

 

 

U

V W

RO2/3

 

 

 

 

nk6_15

 

 

 

 

 

Figure 6-17. Galvanic isolation barriers

6

Page 42
Image 42