Nx Networks NX series user manual 5286, Monitoring menu M1

Models: NX series

1 86
Download 86 pages 56.8 Kb
Page 52
Image 52

7

52(86)

Control keypad

7.3.1Monitoring menu (M1)

The monitoring menu can be entered from the main menu by pushing the Right arrow menu button when the location indication M1 is visible on the first line of the display. How to browse through the monitored values is presented in Figure 7-4.

The monitored signals carry the indication V#.# and they are listed in Table 7-1. The values are updated once every 0.3 seconds.

This menu is only for signal checking. The values cannot be altered here. For changing values of parameters see Chapter 7.3.2.

 

 

R EADY

 

 

Lo ca l

 

 

FreqReference

 

 

13.95 Hz

 

READY

READY

Local

 

Local

Monitor

 

Output frequency

V1

"

13.95 Hz

V14

Figure 7-4. Monitoring menu

 

Code

Signal name

Unit

Description

 

 

 

 

 

 

V1.1

Output frequency

Hz

Frequency to the motor

 

V1.2

Frequency reference

Hz

 

 

V1.3

Motor speed

rpm

Calculated motor speed

 

V1.4

Motor current

A

Measured motor current

 

V1.5

Motor torque

%

Calculated actual torque/nominal torque of the unit

 

V1.6

Motor power

%

Calculated actual power/nominal power of the unit

 

V1.7

Motor voltage

V

Calculated motor voltage

 

V1.8

DC-link voltage

V

Measured DC-link voltage

 

V1.9

Unit temperature

ºC

Heat sink temperature

 

V1.10

Voltage input

V

AI1

 

V1.11

Current input

mA

AI2

 

V1.12

DIN1, DIN2, DIN3

 

Digital input statuses

 

V1.13

DIN4, DIN5, DIN6

 

Digital input statuses

 

V1.14

DO1, RO1, RO2

 

Digital and relay output statuses

 

V1.15

Analogue output current

mA

AO1

 

 

 

 

 

Table 7-1. Monitored signals

Note: Other applications may embody more monitoring values.