\ANO

Type:

Syntax:

Units:

Range:

Default:

Response:

See Also:

Network Analog Output

Network

Product

Rev

<!>n\mANO.i=r

6K

5.3

n =

network server #

 

 

m =

module #

 

 

i =

analog output # on module “m”

 

 

r =

voltage value (VDC)

 

 

n =

1-6

 

 

m =

0-7

 

 

i =

1-2

 

 

r =

-10.00 to +10.00

 

 

n/a

 

 

 

n/a

 

 

 

[ \ANO ], NTIO, \TANO, \TIO

Use the \ANO command to set the voltage of an OPTO22 analog output. The maximum output range can be set from –

10.00VDC to +10.00 VDC. The 6K controller does not recognize the voltage range set on the I/O device (i.e., an \ANO setting of +10 VDC is allowed for an analog output configured with a maximum limit of +5 VDC.)

The controller addresses the OPTO22 I/O locations as follows:

Each I/O bit is addressed by its location on a specific module. (NOTE: I/O points are not addressed by an absolute

32-bit location on the OPTO22.) Digital input and output modules have four I/O points, or channels, and are numbered 1-4. Analog input and output modules have two I/O points, or channels, and are numbered 1-2.

EXAMPLE: OPTO22 is Network Server #2

0

1

2

3

4

5

6

7

Digital

Digital

Digital

Digital

Analog

Analog

Analog

Analog

Input

Input

Output

Output

Output

Output

Input

Input

Module

Module

Module

Module

Module

Module

Module

Module

Input

Input

Output

Output

Output

Output

Input

Input

1

1

1

1

1

1

1

1

Input

Input

Output

Output

Output

Output

Input

Input

2

2

2

2

2

2

2

2

Input

Input

Output

Output

 

 

 

 

3

3

3

3

 

 

 

 

Input

Input

Output

Output

 

 

 

 

4

4

4

4

 

 

 

 

 

2\0IN.3

 

 

 

2\3OUT.2

 

 

 

2\5ANO.1

 

 

2\7ANI.2

 

 

 

 

 

 

 

Example:

; Identify network server #2 as an

OPTO22 unit at IP address

 

2NTIP2,172,54,125,34

 

2NTCONN1

; 172.54.125.34

 

 

 

 

 

 

 

 

 

; Attempt a

connection to network server #2 (OPTO22 unit)

 

2\4NTIO4

; Server #2

(OPTO22), module #4 is

an analog output module

 

2\5NTIO4

; Server #2

(OPTO22), module #5 is

an analog output module

 

2\4ANO.1=4.8

; On Server

#3, module #4, set the

voltage on analog output #1 to

 

 

; +4.8 VDC

 

 

 

 

 

 

 

 

 

 

page 35

Page 39
Image 39
Parker Hannifin GEM6K manual Network Analog Output, Ano , Ntio, \Tano, \Tio