Quatech INTERBUS S manual The numerical format, $*2 , 2 2, 750-476, error, I 1,2

Models: INTERBUS S

1 160
Download 160 pages 62.53 Kb
Page 100
Image 100
error

The numerical format

All analog values will be shown in a unit numerical format. The resolution for 750-476 and 750-478 is 15 Bit plus sign.

750-476, -478

Input voltage

Value

 

 

Status

LED

0-10V

±10V

Binary

Hex.

Dec.

(hex)

error

 

 

 

 

 

 

I (1,2)

>11

>11

0111 1111 1111 1111

0x7FFF

32767

0x42

on

 

 

 

 

 

 

 

>10,5

>10,5

0111 1111 1111 1111

0x7FFF

32767

0x42

off

 

 

 

 

 

 

 

10

10

0111 1111 1111 1111

0x7FFF

32767

0x00

off

 

 

 

 

 

 

 

5

5

0100 0000 0000 0000

0x4000

16384

0x00

off

 

 

 

 

 

 

 

2,5

2,5

0010 0000 0000 0000

0x2000

8192

0x00

off

 

 

 

 

 

 

 

1,25

1,25

0001 0000 0000 0000

0x1000

4096

0x00

off

 

 

 

 

 

 

 

0,0781

0,0781

0000 0001 0000 0000

0x0100

256

0x00

off

 

 

 

 

 

 

 

0,049

0,049

0000 0000 0001 0000

0x0010

16

0x00

off

 

 

 

 

 

 

 

0,0003

0,0003

0000 0000 0000 0001

0x0001

1

0x00

off

 

 

 

 

 

 

 

0

0

0000 0000 0000 0000

0x0000

0

0x00

off

 

 

 

 

 

 

 

<-0,5

 

0000 0000 0000 0000

0x0000

0

0x41

off

 

 

 

 

 

 

 

<-1

 

0000 0000 0000 0000

0x0000

0

0x41

on

 

 

 

 

 

 

 

 

-5

1100 0000 0000 0000

0xC000

49152

0x00

off

 

 

 

 

 

 

 

 

-10

1000 0000 0000 0000

0x8000

32768

0x00

off

 

 

 

 

 

 

 

 

<-10,5

1000 0000 0000 0000

0x8000

32768

0x41

off

 

 

 

 

 

 

 

 

<-11

1000 0000 0000 0000

0x8000

32768

0x41

on

 

 

 

 

 

 

 

Analog Inputs 750-476, 478