Quatech INTERBUS S manual 750-466/000-200 or

Models: INTERBUS S

1 160
Download 160 pages 62.53 Kb
Page 87
Image 87
750-466/000-200 or 750-486:

750-466/000-200 or 750-486:

Input current 4-20mA

>20,5

20

16

12

8

4,0078

4

<3,5

Binary value

0101 0000 0000 0

0101 0000 0000 0

0100 0000 0000 0

0011 0000 0000 0

0010 0000 0000 0

0001 0000 0000 1

0001 0000 0000 0

0001 0000 0000 0

X : without meaning

F : short circuit or

F : open circuit

Ü: overflow

X F Ü

0 0 1

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 0 0

0 1 1

Hex. Dec.

40 01 16385

50 00 20480

40 00 16384

30 00 12288

20 00 8192

1008 4104

1000 4096

1003 4099

Status

42

0

0

0

0

0

0

0

LED

on

off

off

off

off

off

off

on

If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.

Analog￿￿￿￿￿￿￿￿Inputs 750-465,466,486

5

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿:$*2Ç,￿2Ç6<67(0

Page 87
Image 87
Quatech INTERBUS S manual 750-466/000-200 or