Technical Data:
Item Number 750-
Number of inputs
Input current (internal)
Voltage supply
Sensor types
Wire connection
Temperature range
Resolution
Isolation DC/DC
Measuring current
Bit width per channel
Configuration
Operating temperature
Wire connection
Dimensions (mm)WxHxL
Presetting
461, 481,
2
65 mA
via system voltage
PT100, PT 200, PT 500, PT1000, Ni100, Ni120, Ni1000
PT:
0.1°C over the whole area
400V system / power supply
0.5mA type
16 bits: data; 8 bits: control/status
none, optional via software parameter
0°C....+55°C
CAGE CLAMP; 0.08 to 2.5mm2
12 x 64* x 100 (*from upper edge of the carrier rail)
The function module
Linearization is accomplished over the entire measurement range by a microprocessor. The temperature ranges of the above listed RTD types is available to the user. The temperature ranges of the sensors are represented with a resolution of 1 bit per 0.1° C in one word (16 bits). Resulting from this, 0°C corresponds to the hexadecimal value 0000 and 100°C is 03E8 (dez.1000). Temperatures below 0° are represented in two’s complement with a leading ‘1’.
The function module works in the defined temperature range for the PT100 sensors of
A short circuit or an interruption of the RTD wire is transmitted to the bus module and indicated by the red error LED. The green LED identifies that the module is communicating properly with the connected Buscoupler.
Inputfor PT100 | 2 |