The numerical format for Siemens
In addition to the full 16 bit indication of the measured value it is possible to use the Siemens format. The measured value is represented by the most significant 12 Bits. The 3 least significant bits are reserved for diagnostic and status purposes.
Input voltage ±10V
>10
Binary value
0111 1111 1111 1
X : without meaning
F : short circuit or
F : open circuit
Ü: overflow
X F Ü 0 0 1
Hex.
7F F9
Dec.
32761
10
0111 1111 1111 1
0 0 0
7F F8
32760
5
0110 0000 0000 0
0 0 0
60 00
24576
2,5
0101 0000 0000 0
0 0 0
50 00
20480
1,25
0100 1000 0000 0
0 0 0
48 00
18432
0,0049
0100 0000 0000 1
0 0 0
40 08
16392
0
0100 0000 0000 0
0 0 0
40 00
16384
0011 0000 0000 1
0 0 0
30 08
12296
0010 0000 0000 0
0 0 0
20 00
8192
0001 0000 0000 0
0 0 0
10 00
4096
0000 0000 0000 1
0 0 0
00 00
8
0000 0000 0000 0
0 0 1
00 01
1
If you hve questions about the formatting of this data, please contact WAGO for the I/O System technical support.