The numerical format for Siemens

In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 3 least significant Bits are reserved for diagnostic and status purposes. (750-487, 488)

Input

voltage

0-10V

>10

Binary value

0101 0000 0000 0

X : without meaning

F : short circuit or

F : open circuit

Ü: overflow

X F Ü 0 0 1

Hex.

50 01

Dec.

20481

Status

42

10

0101 0000 0000 0

0 0 0

50 00

20480

0

5

0011 0000 0000 0

0 0 0

30 00

12288

0

2,5

0010 0000 0000 0

0 0 0

20 00

8192

0

1,25

0001 1000 0000 0

0 0 0

18 00

6144

0

0,0049

0001 0000 0000 1

0 0 0

10 08

4104

0

0

0001 0000 0000 0

0 0 0

10 00

4096

0

If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.