Numerical format with status information
For fieldbus master, which evaluates status information in the data word, e.g. from Siemens, a variant of the function clamp is available.
The format containes the status in Bit B0 .. B2.
The digitalized measuring value is placed at the position Bit B3 .. B15. The numerical format is equivalent to S5 466.
750-476/000-200
Input |
| Value |
|
| Status | LED |
voltage | Binary |
| Hex. | Dec. |
| error |
±10 V |
| X E O*) |
|
|
| I (1,2) |
> 11 | 0011 1111 1111 1 | 0 0 1 | 0x3FF9 | 16377 | 0x42 | on |
> 10,5 | 0011 1111 1111 1 | 0 0 1 | 0x3FF9 | 16377 | 0x42 | off |
10 | 0011 1111 1111 1 | 0 0 0 | 0x3FF8 | 16376 | 0x00 | off |
5 | 0010 0000 0000 0 | 0 0 0 | 0x2000 | 8192 | 0x00 | off |
2,5 | 0001 0000 0000 0 | 0 0 0 | 0x1000 | 4096 | 0x00 | off |
1,25 | 0000 1000 0000 0 | 0 0 0 | 0x0800 | 2048 | 0x00 | off |
0,0781 | 0000 0000 1000 0 | 0 0 0 | 0x0080 | 128 | 0x00 | off |
0,0049 | 0000 0000 0000 1 | 0 0 0 | 0x0008 | 8 | 0x00 | off |
0 | 0000 0000 0000 0 | 0 0 0 | 0x0000 | 0 | 0x00 | off |
1110 0000 0000 0 | 0 0 0 | 0xE000 | 57344 | 0x00 | off | |
1100 0000 0000 0 | 0 0 0 | 0xC000 | 49152 | 0x00 | off | |
< | 1100 0000 0000 0 | 0 0 1 | 0xC001 | 49153 | 0x41 | off |
< | 1100 0000 0000 0 | 0 0 1 | 0xC001 | 49153 | 0x41 | on |
*) X : without meaning, E : short circuit or open circuit, O : overflow |
| |||||
|
|
|
|
|
|
|
Input |
| Value |
|
| Status | LED |
voltage | Binary |
| Hex. | Dec. |
| error |
| X E O*) |
|
|
| I (1,2) | |
> 11 | 0111 1111 1111 1 | 0 0 1 | 0x7FF9 | 32761 | 0x42 | on |
> 10,5 | 0111 1111 1111 1 | 0 0 1 | 0x7FF9 | 32761 | 0x42 | off |
10 | 0111 1111 1111 1 | 0 0 0 | 0x7FF8 | 32760 | 0x00 | off |
5 | 0100 0000 0000 0 | 0 0 0 | 0x4000 | 16384 | 0x00 | off |
2,5 | 0010 0000 0000 0 | 0 0 0 | 0x2000 | 8192 | 0x00 | off |
1,25 | 0001 0000 0000 0 | 0 0 0 | 0x1000 | 4096 | 0x00 | off |
0,0781 | 0000 0001 0000 0 | 0 0 0 | 0x0100 | 256 | 0x00 | off |
0,049 | 0000 0000 0001 0 | 0 0 0 | 0x0010 | 16 | 0x00 | off |
0,024 | 0000 0000 0000 1 | 0 0 0 | 0x0008 | 8 | 0x00 | off |
0 | 0000 0000 0000 0 | 0 0 0 | 0x0000 | 0 | 0x00 | off |
< | 0000 0000 0000 0 | 0 0 1 | 0x0001 | 1 | 0x41 | off |
< | 0000 0000 0000 0 | 0 0 1 | 0x0001 | 1 | 0x41 | on |
*) X : without meaning, E : short circuit or open circuit, O : overflow
Analog Inputs | 5 |
4;13614<<< | :$*2®,22®6<67(0 |