After elimination of the fault, the buscoupler can only be set to the normal working condition by another POWER ON sequence.

The green I/O LED flashes when accessing the I/O modules internal data channels. After being switched on, the buscoupler queries the configuration of the bus modules but does not carry out a data exchange with the I/O modules. This means that the red I/O LED will extinguish after a faultless startup. The green I/O LED will indicate when data is being exchanged by the Interbus network.

Status and error diagnostics:

The fieldbus LEDs show the state of the bus system. The functions of Interbus S are shown by the LEDs „READY“, „BA“, „RC“ and „RD“.

READY

on

on

on

on

off

BA

off

on

off

off

off

RC

off

off

on

off

off

RD

off

off

off

on

off

Meaning

Buscoupler ready

Fieldbus active; data exchange

incoming connection established

Field bus off

error in cable or master

no function ; no voltage

Help

search error in cable or master

Table 7: Diagnostic LEDs - fieldbus