Quatech INTERBUS S manual The numerical format for Siemens

Models: INTERBUS S

1 160
Download 160 pages 62.53 Kb
Page 105
Image 105
Manual background

The numerical format for Siemens

In addition to the full 16 bit indication of the measured value it is possible to use the ‘Siemens format’. The measured value is represented by the most significant 12 Bits. The 3 least significant Bits are reserved for diagnostic and status purposes. (750-580)

Output voltage 0-10 V

> 10

Binary value

0101 0000 0000 XXXX

Hex.

50 01

Dec.

20481

10

0100 0000 0000 XXXX

40 00

16384

7.5

0011 0000 0000 XXXX

30 00

12288

5

0010 0000 0000 XXXX

20 00

8192

2.5

0001 0000 0001 XXXX

10 08

4104

1.25

0000 1000 0000 XXXX

800

2048

0

0000 0000 0000 XXXX

0

0

If you have questions about the formatting of this data, please contact WAGO for I/O System technical support.