Temperature Ranges of the connectable sensors:

L

-25°C....+900°C

 

K

-100°C...1370°C (Default)

 

J

-100°C...+1200°C

750-462/000-006

E

-100°C...1000°C

750-462/000-008

T

-100°C...+400°C

750-462/000-002

N

-100°C...+1300°C

750-462/000-009

U

-25°C...+600°C

750-462/000-011

B

600°C...+1800°C

750-462/000-007

R

0°C...+1700°C

750-462/000-010

S

0°C...+1700°C

750-462/000-001

mV-Meter

-120 mV...+120 mV

750-462/000-003

Table 1: Temperature ranges of the connectable sensors

Attention: The range of the mV Meter is 0 to 120mV at the moment!

750-469/000-006

750-469/000-008

750-469/000-002

750-469/000-009

750-469/000-011

750-469/000-007

750-469/000-010

750-469/000-001

750-469/000-003

LED functions:

green LED: Function ON: Normal

OFF: Watchdog-Timer Overflow

If the PLC does not transmit processing data for 100 ms the green LED stops lightning.

red LED: Error

ON: Over- or underrange or broken wire (bei 750-469)

OFF: voltage is in the measuring range

Input￿￿￿￿￿￿￿￿for thermocouple modules 750-462,469

3

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿:$*2Ç,￿2Ç6<67(0

Page 81
Image 81
Quatech INTERBUS S manual Temperature Ranges of the connectable sensors, LED functions