Instructions
Updating of documentation
Contents of instructions
Subject to technical changes
Content
Symbol definitions
Safety and general instructions
Designated use
Hazard definitions
What to do if YOU Smell GAS
Following instructions must be followed
Disposal
Follow these instructions for the space heating water
Tools, materials and additional equipment
Regulations and guidelines
Room sealed boiler
Description of the boiler
Condensing
Modulating
Transportation
Packaging and transportation
Scope of delivery
Requirements for the installation room
Installation
Fitting the boiler
E75CP
Dimensions
Connection for combustion air supply and vent system
Plumbing Kit
Plumbing Kits
Low Loss Header
Clearances from boiler
CSA
Technical specifications
Central heating system
Connecting the boiler
Compression fittings
Plumbing Kit installation
Installation & Servicing Instructions Rinnai E
Low water cut off
Safety valve
Expansion tank
With the boiler
Gas supply connection
Underfloor heating system plastic pipes
Gas piping
Gas connection with natural gas
Propane Supply Pressure Requirements
Gas connection with propane gas
Condensate drain pipe
Hot water supply
Intake / Exhaust Guidelines
Vent system and air supply system
To the boiler. See the list on
Agency
2a Examples vent and air supply systems concentric
2b Examples vent and air supply systems parallel
Concentric system see
Installation of the vent system
Parallel system see
Room Air System outdoor combustion air
Terminal positions
Recommended vent/air intake terminal position
Item Description Flue Material United States
Occur to building products in the vicinity see
Dimensioning of the exhaust and air intake duct
Calculation of equivalent length vent system
Combustion air and vent piping lengths
Parallel system
Total equivalent length Concentric system
Boiler type E75 E110
Calculation of compensation factor
Unconfined Space
Room Air System indoor combustion air
Location
Confined Space
Louvers and Grills
Using Outdoor Air For Combustion
Using Indoor Air For Combustion
Electrical connections
Connecting incoming power
Are used must have a Volt free contact
Connection terminal E-Series
Electrical diagram
Electrical ladder diagram
Good-state or standard read out
Boiler controls
Technical read out
Operation indication
Explanation of the function buttons
Requirements of the water system
Freeze protection
Filling the heating system
With water will have to be done
Close main gas shut off valve
Do not try to light the burner by hand
Altering adjustments
Adjustments
Press the Mode-button for 5 seconds
Press the STORE-button to confirm the code code blinks1
Parameter Mode
Outdoor reset
Isolating the boiler
Activating factory settings green button function
Boiler and/or the installation
Commissioning
Start up of the boiler
Testing for gas leaks
Testing the Ignition Safety shut off device
Boiler needs maintanance
Checking for contamination
Type of boiler
Checking of the zero pressure control
Follow the next procedure
Checking the O2
Measuring the ionization current
Installing the casing
Periodic examination of venting systems and boiler
Maintenance
Inspection
Technician
Visual inspection for general signs of corrosion
Checking and adjusting the gas/air ratio
Measuring the inlet gas pressure
Carrying out a pressure test of the heating system
Replace the gasket with a new one
Maintenance activities
Condensate tray
Condensate trap
Visual inspection of the flame
Warranty
G K
Parts of the boiler
Error indication short reference
Blocks and Errors
Block
External safety contact is active
Blocks
Check flow through the installation
Check flow through the boiler and DHW fascility
Execute Parameter-Reset
Check the sensors NTC 1 and NTC
Check the boiler Pump
Check the main Power supply
Rectify the short-circuit If necessary replace this part
Errors
Error
Check Disconnected Components for short-circuiting
Disconnect voltage from the boiler and check the fuse F2
Check the 24 Volt Connection
Gas
Check the data in Error mode
Ionisation flow Ionisation cable or O2 setting
Rectify the prece Ding error
Software error con Trol unit
Reset the boiler
Error persists After reset Software error Control unit
Software error Control unit
Error
Check Disconnected parts for wear and tear
Remove Voltage from the boiler and check fuse F2
Check the 24 Volt Connections
Software error Control unit
If necessary Replace the flow Sensor
Temperature of 36 is displayed at position
Check flow sensor NTC1
Check actual flow temperature
Check return Sensor NTC
Check actual return temperature
Wiring and voltage are OK and error is repeated
Fuse is working and the error is repeated
Fan is not Spinning
If necessary Replace the fan
Replace Sensor
Check the wiring
Wiring is OK but the error is repeated
Shut down of return sensor T2
Contact for supply sensor T1 open
Check the data Error mode
Software error Control unit
Central heating but no hot water
Other errors
Hot water but no central heating
Key of the central heating program is not switched on
RS100 with outdoor Sensor Room sensor-On
Three-port valve is not circulating to central heating
Key pump program Is on
Hot and cold water Connection to the boiler Mixed up
Insufficient quantity of hot water
Incorrect flow reducing Valve
Absence Positive results
Flow reducing valve
Temperature drop of the DHW
DHW power for the boiler is set too low
Radiators do not get hot enough or warming up takes too long
Incorrect choice Installation
Parts casing E-Series
Spare parts
Description
Installation Manual E-SERIES
Parts heat exchanger E-Series
OSS1 OSS2 Clamp BAR TOP Part H.EX. Long
Parts rear wall E-Series
OSS1 OSS2
Parts pipes E-Series
Description
166 167
Parts electrical components E-Series
101
Vent Products
Parts list vent system
Heatfab
Rinnai/ Ubbink
103
Common venting guidelines
104
105
106
107
800000012 9/2009