Rinnai E75CP, E110CP check setting of room thermostat or RS101, supply water temperature too low

Models: E75CP E110CN E75CN E110CP

1 108
Download 108 pages 9.51 Kb
Page 91
Image 91
check setting of room thermostat or RS101

16.6 Radiators do not get hot enough or warming up takes too long

radiators do not get hot enough or warming them up takes too long

check setting of room thermostat or RS101

supply water

temperature too low

Check setting PARA chapter Step No. 1 and increase if necessary

incorrect choice of

installation

PARA chapter Step No. 2 if necessary change

installation resistance

too high (given an

average T > 36°F the boiler decreases the load)

see installation instructions

check / clean water filter check dimensions of pipes

Installation & Servicing Instructions Rinnai E-Series

91

Page 91
Image 91
Rinnai E75CP check setting of room thermostat or RS101, supply water temperature too low, incorrect choice of installation