15.2 Errors

Installation & Servicing Instructions Rinnai E-Series

15.2 Errors

A detected error is indicated on the display by an Error message. Error messages are permanent locks which can only be removed by pressing the reset key. The controller will make every possible attempt to prevent the lock. Below is a summary of the Errors.

Error15.2.1Error 00 with one figure on the last 2 characters.

15.2.1Error 00

incorrect flame formation.

boiler has not been

burning but an

ionisation flow (flame) has still been detected

check whether the ionisation cable and/or the electrode are responsible for a possible short- circuit. Remove the plugs from the ionisation cable connected to the control unit and to the electrode. Now using a universal meter take a measurement between the ionisation connection and the ground, now refit it part by part until a short-circuit takes place.

rectify the short-circuit

and if necessary replace this part.