6.7.6 Combustion air and vent piping lengths.
In the table below you find the maximum equivalent pipe length of the vent/air system based on 3" diameter. These lengths are for single pipe (room air), twin pipe, and concentric venting systems.
| Boiler type | 3” Max Vent equivalent length | 3” Max Air equivalent length |
| E75 | 100 feet | 100 feet |
| E110 | 100 feet | 100 feet |
Equivalent vent length | table 9 |
Calculation of equivalent length vent system
Choose the vent type and fill out the corresponding table.
*When determining equivalent combustion air and vent length, add 6 feet for each 90° elbow, 3 feet for each 45° elbow, 5 feet for the concentric terminal in the Parallel System, and 2 feet for the concentric terminal in the Concentric System .
Parallel system
Length tube | Number of | Number of | Concentric | Total | Multiply with | Equivalent |
| elbows 90° | elbows 45° | terminal |
| factor | length |
| x 6* | x 3* | Add 5 ft.* |
|
|
|
Combustion air |
|
|
|
|
|
|
ft | ft | ft | ft | ft | 0.5 | ft |
Vent |
|
|
|
|
|
|
ft | ft | ft | ft | ft | 0.5 |
Total equivalent length
Concentric system
ft ft
| Length concentric | Number of | Number of | Concentric | Total |
| Multiply with Total equivalent | ||||||
| tube, boiler to roof | elbows 90° | elbows 45° | terminal |
|
|
|
|
| factor | length | ||
| horizontal |
| x 6* | x 3* | Add 2 ft.* |
|
|
|
|
|
| ||
| ft |
| ft | ft |
| ft |
|
| ft |
| 1.0 |
| ft |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Example of calculation: |
|
|
|
|
|
|
|
|
| |
|
|
| Twin tube (parallel) with terminal |
|
|
|
|
|
|
|
| ||
|
|
|
| Combustion air length | : 24 ft | with elbow 3 x 90° |
| ||||||
|
|
|
| Vent length |
| : 24 ft | with elbow 2 x 90°, elbow 2 x 45° |
| |||||
Installation & Servicing Instructions Rinnai |
| Calculation: |
|
|
|
|
|
|
|
|
| ||
| Equivalent Air Length | : (24+3x6+2) x 0.5 | = | 23 ft |
| ||||||||
| Equivalent Vent Length | : (24+2x6+2x3+2) x 0.5 | = | 23 ft +Total = | 46 ft. | ||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|