15.2.2Error 01
24 Volt
disconnect voltage from the boiler and check the fuse F2
as a result of a 24 Volt
check the 24 Volt
connection
remove all plugs with 24 Volt connections such as: fan, pump, any
check the
disconnected
components for short-circuiting
switch on power again to the control unit with the components disconnected. Reconnect the components, which have been checked and are working.
rectify the short- circuit or replace the