15.2.12Error 18
Temp | NTC 12K |
°F | (12k:/77°F) |
supply sensor T1 return sensor T2 DHW sensor T3 outside sensor T4 flue gas sensor T5
98,000 | |
90,000 | |
3.2 | 82,000 |
6.8 | 74,000 |
10.4 | 66,000 |
14 | 58,000 |
17.6 | 53,500 |
21.2 | 49,000 |
24.8 | 45,000 |
28.4 | 40,500 |
32 | 36,000 |
35.6 | 33,500 |
39.2 | 30,900 |
42.8 | 28,200 |
46.4 | 25,600 |
50 | 23,000 |
53.6 | 21,400 |
57.2 | 19,900 |
60.8 | 18,100 |
64.4 | 16,600 |
68 | 15,000 |
71.6 | 14,000 |
75.2 | 12,900 |
78.8 | 11,900 |
82.4 | 10,850 |
86 | 9,800 |
89.6 | 9,100 |
93.2 | 8,500 |
96.8 | 7,900 |
100.4 | 7,200 |
104 | 6,500 |
113 | 5,600 |
122 | 4,600 |
131 | 4,000 |
140 | 3,400 |
158 | 2,300 |
176 | 1,700 |
194 | 1,300 |
212 | 950 |
Resistance table
Signal maximum flow water temperature exceeded (T1 > 212°F).
check actual flow temperature
suddenly increase caused by completely hydraulic shut off of the boiler (filter, pump, thermostat valve, service valve)
check flow sensor NTC1
measure the resistance value (see table)
exchange defective part if necessary.
Change control unit when error persists