Rinnai E110CN, E110CP, E75CN 15.2.12Error, check actual flow temperature, check flow sensor NTC1

Models: E75CP E110CN E75CN E110CP

1 108
Download 108 pages 9.51 Kb
Page 78
Image 78
15.2.12Error 18

Installation & Servicing Instructions Rinnai E-Series

15.2.12Error 18

Temp

NTC 12K

°F

(12k:/77°F)

supply sensor T1 return sensor T2 DHW sensor T3 outside sensor T4 flue gas sensor T5

-4

98,000

-0.4

90,000

3.2

82,000

6.8

74,000

10.4

66,000

14

58,000

17.6

53,500

21.2

49,000

24.8

45,000

28.4

40,500

32

36,000

35.6

33,500

39.2

30,900

42.8

28,200

46.4

25,600

50

23,000

53.6

21,400

57.2

19,900

60.8

18,100

64.4

16,600

68

15,000

71.6

14,000

75.2

12,900

78.8

11,900

82.4

10,850

86

9,800

89.6

9,100

93.2

8,500

96.8

7,900

100.4

7,200

104

6,500

113

5,600

122

4,600

131

4,000

140

3,400

158

2,300

176

1,700

194

1,300

212

950

Resistance table NTC-Sensors

Signal maximum flow water temperature exceeded (T1 > 212°F).

check actual flow temperature

suddenly increase caused by completely hydraulic shut off of the boiler (filter, pump, thermostat valve, service valve)

check flow sensor NTC1

measure the resistance value (see table)

exchange defective part if necessary.

Change control unit when error persists

78

Page 78
Image 78
Rinnai E110CN 15.2.12Error, check actual flow temperature, check flow sensor NTC1, exchange defective part if necessary