14.2.1Visual inspection for general signs of corrosion
-Check all gas and water pipes for signs of corrosion.
-Replace any pipes that are corroded.
14.2.2Measuring the ionization current
See subsection 12.6 “Measuring the ionization current".
14.2.3Measuring the inlet gas pressure
See subsection 6.4.1 and .2 “Gas connection with natural gas" and "Gas connection with propane”.
14.2.4Checking and adjusting the gas/air ratio
See subsection 12.4 “Checking of the zero pressure control”.
14.2.5Testing for gas leaks
See subsection 12.1 “Testing for gas leaks”.
14.2.6Carrying out a pressure test of the heating system
See chapter 9.2 “Filling the heating system”.
14.2.7Checking venting systems
Check the following points:
-Is the prescribed combustion air/flue system used?
-Have the instructions for configuring the flue system as specified in the relevant Installation instruction for the flue gas system been observed?
-Check air intake and flue gas for obstruction or damage.