6.7.4Recommended vent/air intake terminal position

i

!

NOTICE

CAUTION

Terminals should be positioned as to avoid products of combustion entering openings into buildings or other vents.

Maintain 12” of clearance above the highest anticipated snow level or grade or, whichever is greater. Please refer to your local codes for the snow level in your area.

!

i

i i

i

CAUTION

The termination shall be at least 4 feet (1,220 mm) for the US and 6 feet (1,830

 

mm) for Canada distance from electric meters, gas meters, regulators and

 

relief equipment. (for room air application only)

NOTICE

Horizontal vent systems should always be installed sloping towards the

boiler (min. 21 mm/m, 1/4 “/ feet), in order to avoid condensate retaining in

 

the vent system. With the condensate running back to the boiler the risk of

 

ice forming at the terminal is reduced.

NOTICE

The whole route of the vent system must be installed upwards, never

 

downwards, completely nor partly.

NOTICE

Place pipe supports every 4 feet (1219 mm) of horizontal run, beginning with

 

the support near the boiler to prevent movement in fittings and allow boiler

 

to be free from any strain or weight on boiler or fittings.

NOTICE

The terminal should be located where dispersal of combustion products is

 

not impeded and with due regard for the damage or discolouration that might

 

occur to building products in the vicinity (see fig 14 and 15).

E-Series

 

 

Approval Codes for Installation

Item Description

Flue Material

United States

 

Plastic Vent and/or air

PVC Schedule 40

ANSI/ASTM D1785

 

pipes and fittings

PVC - DWV

ANSI/ASTM D2665

 

 

CPVC Schedule 40

ANSI/ASTM F441

 

Plastic Pipe cement and

PVC

ANSI/ASTM D2564

 

primer

CPVC

ANSI/ASTM F493

 

 

Item Description

Flue Material

Manufacturer

US/CAN

 

Flue system

 

Stainless steel vent

 

 

 

concentric

Saf-T Vent SC

 

systems

AL29-4C

Heat Fab

UL1738

twin pipe

Saf-T Vent EZ Seal

 

Plastic Vent and/or air

 

 

 

 

Rolux Condensing

 

pipes and fittings

PPS

Ubbink

 

 

Vent System

Approval codes for installation of venting system

 

 

 

table 7

Installation & Servicing Instructions Rinnai

30

12" (300 mm)

 

minimum

12" (300 mm)

 

minimum

EXHAUST

 

INTAKE

12" (300 mm)

 

 

minimum

12" (300 mm)

 

12" (300 mm)

minimum

 

minimum

 

 

Terminal positions PVC

 

figure 15

 

Fittings or Piping Equivalent

 

 

 

feet

m

 

45 degree elbow

3

0.91

 

90 degree elbow

6

1.83

 

plastic pipe per foot

1

0.30

 

concentric vent kit

3

0.91

Equivalent friction loss of PVC/CPVC

table 8

Page 30
Image 30