Rinnai E110CN, E110CP, E75CN, E75CP user manual Adjustments, Altering adjustments, i NOTICE

Models: E75CP E110CN E75CN E110CP

1 108
Download 108 pages 9.51 Kb
Page 46
Image 46
10 Adjustments

10 Adjustments

When the boiler is installed it is ready for use. All adjustments of the boiler control are already pre-programmed for a heating system with radiators/convectors with a supply temperature of 185°F. The adjustments are described in the Parameter chapter on page 44.

In certain cases parameters have to be altered in case of :

-Lower supply temperature

-High altitude/long vent length

Read through the Parameter chapter to adjust the boiler to its installation.

Contact Rinnai in case of doubt.

i NOTICE

Only qualified personel who are trained for servicing these boilers are permitted

to make alterations in the controller to calibrate the boiler to the installation.

11.1 Altering adjustments

STEP 1 Press the Mode-button for 5 seconds.

The display shows COdE followed by an arbitrary number;

STEP 2

Press by means of the + or the - button until the code C123 is shown;

 

Press the STORE-button to confirm the code (code blinks1 x).

STEP 3

 

Now you have acces to the installer level. There are 4 chapters:

 

 

Parameters

 

 

 

 

 

 

 

Information chapter (no adjustments possible)

 

 

 

 

 

 

Service chapter

 

 

 

 

 

 

Error-chapter (no adjustments possible)

 

 

 

Installation & Servicing Instructions Rinnai E-Series

STEP 4

STEP 5

STEP 6

STEP 7

STEP 8

i NOTICE

The content of the chapters is described on the following pages.

Press briefly the MODE-button to select one of the 4 chapters, i.e. PARA;

Press once or more briefly on the STEP-button to select a Parameter (parameter visible on the left, value on the right) ;

Alter the value, if necessary/possible, by means of the + or the - button

Press briefly on the STORE-button to confirm the alteration.

When you have to change more values, repeat from step 5.

Press once or more on the MODE-button until StBY or Good is shown:

After a few seconds the text StBY will be replaced by the technical read-out or Good-state (Depending from the position the acces code is entered)

When you want to return from an arbitrary position to the original read out press once or more on the MODE-button until StBY is shown.

If no single button is used within 20 minutes the display will return automatically to its original read-out (Good state or technical read out)

46

Page 46
Image 46
Rinnai E110CN, E110CP, E75CN, E75CP user manual Adjustments, Altering adjustments, i NOTICE