12.3 Checking for contamination

12.3 Checking for contamination

i NOTICE

In order to be able to check the boiler for contamination in the following running

years it is advisable to measure the maximum air displacement in the boiler

 

when putting the boiler into operation. This value can be different with each

 

type of boiler.

 

 

 

In order to be able to measure this value follow the next procedure:

 

-

Press the MODE-button

for 5 seconds.

 

 

- The display will show COdE followed by an arbitrary number;

 

-

Select by means of the

or the

button the code C123;

 

- Press the Store-button to confirm the code (code blinks 1 x);

 

- Press the MODE-button until SERV is shown;

 

- Press the STEP-button until 2 is shown;

 

 

 

alternately 2 and OFF will be shown.

 

 

- Turn open the upper measuring nipple on the gas valve (fig. 18);

 

- Connect the hose of the digital pressure gauge to the upper measuring nipple of

 

 

the gas valve

 

 

Installation & Servicing Instructions Rinnai E-Series

Check point contamination

 

 

figure 18

 

 

 

 

-

Press the

button until the maximum value is achieved;

 

 

 

 

The fan will function to its maximum revolutions (burner stays off)

i

NOTICE

 

- Measure the under pressure and write down this value.

 

 

At the next servicing visit this value may drop 20% of its original value on

 

 

 

 

the moment of installation. When this value is dropped more than 20% the

 

 

 

 

boiler needs maintanance.

 

 

 

-

Press the

button until OFF is shown (keep button pressed)

 

 

 

 

 

 

 

 

With this the procedure is finished.

 

 

 

 

 

52