Parameter Mode
PARA | FACTORY | DESCRIPTION | RANGE |
. | . | . | . |
1 | 186°F | maximum supply temperature CH | 68 - 186°F |
2* | 00 | type of CH installation: |
|
|
|
| 01 DO NOT USE |
|
| radiators with large surface areas or underfloor heating as additional heating: | 02 |
|
| T max. supply 158°F K factor heating curve 1.8; gradient 10°F/min; gear differential 10°F |
|
|
|
|
|
|
| under floor heating with radiators as additional heating: | 03 |
|
| T max. supply 140°F; K factor heating curve 1.5; gradient 8°F/min; gear differential 8°F |
|
|
|
|
|
|
| full under floor heating: | 04 |
|
| T max. supply 122°F; K factor heating curve 1.0; gradient 6°F/min; gear differential 6°F |
|
|
|
|
|
3 | max. | maximum power CH in kW (.. x3415 = .. BTU/hr) | |
4* | 00 | control principal with on / off thermostat: |
|
|
| 100 % on / off thermostat | 00 |
|
| 100 % on / off weather dependant | 01 |
5* | 2.3 | heating curve | 0.2 - 3.5 |
6* | 1.4 | heating curve exponent (see also heating curve graph) | 1.1 - 1.4 |
7* | 14°F | heating curve climate zone (see also heating curve graph) | |
10* | 0°F | fine adjustment heating curve day temperature | |
11* | 0°F | fine adjustment heating curve night temperature | |
14 | 10°F/min. | gradient speed °F/min. | 0 - 28°F/min. |
15* | 00 | Booster after night decrease*: |
|
|
| no | 00 |
|
| yes | 01 |
23 | 26°F | Frost Temperature | |
27 | 32°F | Minimum | 0 - 158°F |
31 | 132°F | DHW temperature | 68 - 176°F |
36 | 20 | Type of three way valve DHW fascility |
|
|
| VC 2010 / VC 8010 | x0 |
|
| Flowswitch | 2x |
43 | max. | Maximum power DHW in kW (.. x3415 = .. BTU/hr) | |
49 | 100% | Maximum pump capacity heating | 100 % |
73 | 0 | Altitude and venting CFT. See chapter 6.7.7 | 0 - 100 |
89 | 00 | Address |
|
|
| No function | |
|
| Bus thermostat | 00 |
90 | 01 | Display reading | 00 |
|
| °C and Bar | |
|
| °F and PSI | 01 |
. | . | . | . |
Info Mode |
|
| |
INFO | FACTORY | DESCRIPTION | RANGE |
. | . | . | . |
1 | °F | supply water temperature T1 |
|
4 | °F | return water temperature T2 |
|
5 | °F | DHW temperature T3 |
|
7 | °F | outdoor temperature T4 |
|
8 | °F | flue gas temperature T5 (optional sensor) |
|
16 | % | actual power in % |
|
17 | kW | actual power in kW (.. x3415 = .. BTU/hr) |
|
18 | kW | actual load in kW (.. x3415 = .. BTU/hr) |
|
20 |
| indication bus communication |
|
21 | GJ | consumption total in GJ (.. x 33 = .. m3) |
|
22 | GJ | consumption CH in GJ (.. x 33 = .. m3) |
|
23 | GJ | consumption DHW in GJ (.. x 33 = .. m3) |
|
24 | h | total number of burner run hours |
|
25 | h | number of burner run hours CH |
|
26 | h | number of burner run hours DHW |
|
32 | h | total number of hours counter |
|
37 | h | total number of run hours pump CH and DHW |
|
46 | h | within how many hours is service required |
|
. | . |
| . |