15.1.2Block 11
maximum average DT of supply and return sensor for central heating is repeatedly exceeded. Operation is normally possible for the hot water supply during the block. The pump continues to operate at minimum capacity during the block.
check flow through the installation
seetheinstallationinstructionsforthehydraulic connections to the boiler
possible causes: (radiator)
activeted room sensor (RS101) in non leading room (closed thermostatic radiator valves?)
check pump height.
check minimum and maximum Temperature difference in Parameter Step 46 + 47.
Installation & Servicing Instructions Rinnai
64