Rinnai E110CP, E75CN, E110CN, E75CP user manual 15.1.2Block, check flow through the installation

Models: E75CP E110CN E75CN E110CP

1 108
Download 108 pages 9.51 Kb
Page 64
Image 64
15.1.2Block 11

15.1.2Block 11

maximum average DT of supply and return sensor for central heating is repeatedly exceeded. Operation is normally possible for the hot water supply during the block. The pump continues to operate at minimum capacity during the block.

check flow through the installation

seetheinstallationinstructionsforthehydraulic connections to the boiler (3-Way-Thermostatic valve, Plumbing Kit installed?)

possible causes: (radiator) shut-off valves closed or blocked water filter

activeted room sensor (RS101) in non leading room (closed thermostatic radiator valves?)

check pump height.

check minimum and maximum Temperature difference in Parameter Step 46 + 47.