Samson 5476 manual Operation, Select datapoint for times-of-use Display

Models: 5476

1 114
Download 114 pages 58.6 Kb
Page 13
Image 13
Select datapoint for times-of-use.

0

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15 16

17 18 19 20 21 22

23 24

1

0

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15 16

17 18 19 20 21 22

23 24

 

 

 

 

 

 

 

 

 

 

 

 

 

0

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15 16

17 18 19 20 21 22

23 24

START

Operation

Select datapoint for times-of-use.

Display: Manual background

Activate editing mode for times-of-use.

Display: 1–7

Select period/day for which the times-of-use are to be valid:

1–7 = Monday to Sunday 1–5 = Monday to Friday 6–7 = Saturday to Sunday

1 = Monday, 2 = Tuesday, …, 7 = Sunday

Activate editing mode for period/day.

Display: START; Manual background blinks.

Edit start time (steps of 30 minutes).

Confirm start time. Display: STOP

Edit stop time (steps of 30 minutes).

Confirm stop time. Display: START

The second time-of-use is set like the first time-of-use.

To set the times-of-use for each day, repeat the instructions in the fields highlighted in gray.

Exit the datapoint for times-of-use.

Return to the operating level.

Note!

Do not use the 1–7 , 1–5 und 6–7 menus to check the programmed times-of-use. On opening this period, the times-of-use are reset to their default settings.

Note!

The controller automatically returns to the operating level if the keys are left unpressed for five minutes.

EB 5476 EN 13