Appendix
Function | WE | Configuration |
Flow rate limitation | OFF | FB30 = ON |
2.0 m3 h Maximum limit / 0.01 to 650 m3 h
2.0m3 h Maximum limit for heating* / 0.01 to 650 m3 h
2.0m3 h Maximum limit for DHW / 0.01 to 650 m3 h
2.0m3 h Minimum limit/ 0.01 to 650 m3 h
1.0Limiting factor / 0.1 to 10.0
*Does not need to be set on selecting “At“
Parameter* | WE | Range of values |
Maximum limit for heating, points 1 to 4 | 2.0 m3/h | 0.01 to 100 m3/h |
* Parameter only needs setting with FB30 = ON, select “At“
Capacity limitation
The settings which are to made for the capacity limitation are mainly contained in function block FB31 as function block parameters. Only after selecting the type of limitation “At“ for outdoor temperature dependent limitation (which automatically means a
Function | WE | Configuration |
Meter bus | OFF | FB29 = ON |
| 254** | Meter bus address for WMZ 1 to 3 |
| 1434 | 255 |
| Cont | Model code WMZ 1 to 3 / 1434, CAL3, APAtO, SLS |
|
| Reading mode WMZ 1 to 3 / 24h, Cont, CoiL |
Capacity limitation | OFF | FB31 = ON |
| 15 kW | Maximum limit / 0.01 to 6000 kW |
| 15 kW | Maximum limit for heating* / 0.1 to 6000 kW |
| 15 kW | Maximum limit for DHW / 0.1 to 6000 kW |
| 1.0 | Limiting factor / 0.1 to 10.0 |
*Does not need to be set on selecting “At“
**WE for WMZ2 and 3: 255
Parameter* | WE | Range of values |
Maximum limit for heating, points 1 to 4 | 15 kW | 0.1 to 6000 kW |
EB 5476 EN 73