Installation
for details on which listed heat meters fulfill this criterion and can be used for limitation pur- poses.
In case of
A system with simultaneous room heating and DHW heating requires maximum energy. A system with a fully charged storage tank which performs only room heating requires less
energy.
A system which suspends room heating during DHW heating requires less energy.
As a result, three different maximum limit values can be specified: Max. limit value to determine the absolute upper limit
Max. limit value for heating for exclusive operation of the room heating Max. limit value for DHW for exclusive operation of the DHW heating
In all systems without DHW heating or without heating circuit, only the Max. limit value for the flow rate or capacity can be set.
Flow rate limitation
The settings which are to made for the flow rate limitation are mainly contained in function block FB30 as function block parameters. Only after selecting the type of limitation “At“ for out- door temperature dependent limitation (which automatically means a
Function | WE | Configuration |
Meter bus | OFF | FB29 = ON |
| 254** | Meter bus address for WMZ 1 to 3 |
| 1434 | Model code WMZ 1 to 3 / 1434, CAL3, APAtO, SLS |
| Cont | Reading mode WMZ 1 to 3 / 24h, Cont, CoiL |
** WE for WMZ2 and 3: 255