Samson 5476 manual 6.9Priority circuit Anl 4, 5, 6, 7, 8 and, Reverse control, Set-backoperation

Models: 5476

1 114
Download 114 pages 58.6 Kb
Page 55
Image 55
6.9Priority circuit (Anl 4, 5, 6, 7, 8 and 11)

Functions of the DHW circuit

Once a parallel pump operation cycle has been activated and the time for Stop parallel opera- tion has elapsed, system deviations greater than 5 °C cause the controller to suspend parallel operation for 10 minutes and to apply priority operation.

Function

WE

Configuration

Parallel pump operation

OFF

FB9 = ON, PU

 

10 min

Stop parallel operation / 2 to 10 min

 

 

 

Note!

In system Anl 9, the control valve of the underfloor heating circuit is always closed with the function block setting FB9 = OFF. With the setting FB9 = ON, select “PU“ to ensure it remains in control operation even the parallel operation has been interrupted due to system deviations.

6.9Priority circuit (Anl 4, 5, 6, 7, 8 and 11)

In many district heating systems with primary DHW heating, the allotted amount of water is only intended to supply the heating system. As a result, the capacity required for DHW heating needs to be taken from the heating system when great heating loads occur; and this, until DHW heating has been concluded.

Nevertheless, heating operation is not simply to be interrupted. Only the amount of energy re- quired for DHW heating is to be deducted. This can be achieved by using the priority functions Reverse control and Set-back operation.

6.9.1 Reverse control

The capacity demand of the heating circuit is reduced when there is a system deviation of more than 5 °C in the DHW circuit. This is achieved by the three-step output of the DHW circuit work- ing in the opposite direction compared to the heating circuit control valve.

The amount of time in which the priority for the DHW circuit is given is set in the Priority in case of deviation parameter.

Function

WE

Configuration

Priority for

OFF

FB8 = ON, select “In“

DHW circuit

10 min

Priority in case of deviation / 2 to 10 min

6.9.2 Set-back operation

The heating circuit is set back to reduced operation for 20 minutes when a system deviation of more than 5 °C arises in the DHW circuit. Its capacity demand is reduced by the value in

EB 5476 EN 55

Page 55
Image 55
Samson 5476 6.9Priority circuit Anl 4, 5, 6, 7, 8 and, Reverse control, Set-backoperation, Functions of the DHW circuit