Samson 5476 7.7On/off control, 7.9Processing of external demand in RK1, System-widefunctions

Models: 5476

1 114
Download 114 pages 58.6 Kb
Page 60
Image 60
7.7On/off control

System-wide functions

7.7On/off control

The flow temperature can be controlled by an on/off signal. The controlled valve is opened when the flow temperature falls below the set point by T = 0.5 x Hysteresis. When the flow tem- perature exceeds the set point by T = 0.5 x Hysteresis, the control valve is closed. The greater the Hysteresis selected, the lower the switching frequency.

Function

WE

Configuration

On/off control for RK1/RK2

ON

FB10/FB17 = OFF

 

5 °C

Hysteresis / 1 to 30 °C

7.8Releasing a control circuit over the binary input

The release of a control circuit using the binary output only becomes effective when the respec- tive control circuit is in automatic mode (icon ).

The released control circuits always work in automatic mode; the deactivated control circuit be- haves as if it were in frost protection mode if the outdoor temperature requires it. The control cir- cuit can be released via the binary input when the binary input is open (BE = ON).

Function

WE

Configuration

Releasing a control circuit

OFF

FB25 = ON, FErn

 

 

 

Note!

The function cannot be selected in systems Anl 4, 5 and 9 with solar system and in system Anl 11 with VF3.

7.9Processing of external demand in RK1

Regardless of the operating mode, except form manual mode, of the control circuit RK1, the controller uses the Minimum flow temperature for external demand when the binary input is closed (BE1 = ON). The DHW heating from the secondary circuit and demands of the heating circuit which are higher than the Minimum flow temperature for external demand have priority. In systems Anl 7 and 8, a mixing control is not active, just the set point of the heating circuit changes.

The deactivated binary input (BE1 = OFF) does not have any effect on the control.

Function

WE

Configuration

External demand over BE1

OFF

FB25 = ON, bed

 

20 °C

Minimum flow temperature for external demand / 20 to 130 °C

 

 

 

60EB 5476 EN

Page 60
Image 60
Samson 5476 manual 7.7On/off control, 7.9Processing of external demand in RK1, System-widefunctions