5.1.2 4-point characteristic

Functions of the heating circuit

5.1.2 4-point characteristic

The 4-point characteristic allows you to define your own heating characteristic.

It is defined by 4 points for the Outdoor temperature, the Flow temperature and the Return flow temperature. The Set-back difference at points 2 and 3 indicates how much the flow temperature is reduced outside the times-of-use. The Max. flow temperature and Min. flow temperature pa- rameters mark the upper and lower limits of the flow temperature.

P1 to P4

Points 1 to 4

tVL

Flow temperature

tA

Outdoor temperature

... min

Minimum flow temperature

... max

Maximum flow temperature

-----

Set-back characteristic

Fig. 3 · 4-point characteristic

 

Function

WE

 

 

Configuration

Characteristic

OFF

 

 

FB19 = ON

 

 

 

 

Parameters

WE

WE*

Range of values

Outdoor temperature, point 1

–15 °C

–15 °C

–30 to

20 °C

Outdoor temperature, point 2

–5 °C

–5 °C

 

 

Outdoor temperature, point 3

5

°C

5

°C

 

 

Outdoor temperature, point 4

15

°C

15

°C

 

 

Flow temperature, point 1

70 °C

50 °C

20 to 130 °C

Flow temperature, point 2

55

°C

40

°C

 

 

Flow temperature, point 3

40

°C

35

°C

 

 

Flow temperature, point 4

25

°C

20

°C

 

 

Return flow temperature, point 1

65

°C

 

20 to

90 °C

Return flow temperature, point 2

50

°C

 

 

 

Return flow temperature, point 3

35

°C

 

 

 

Return flow temperature, point 4

20

°C

 

 

 

Set-back difference, points 2, 3

20

°C

5

°C

0 to

50 °C

Max. flow temperature

90

°C

50

°C

20 to 130 °C

42EB 5476 EN