Functions of the heating circuit
5.1.2 4-point characteristic
The
It is defined by 4 points for the Outdoor temperature, the Flow temperature and the Return flow temperature. The
P1 to P4 | Points 1 to 4 |
tVL | Flow temperature |
tA | Outdoor temperature |
... min | Minimum flow temperature |
... max | Maximum flow temperature |
Fig. 3 · |
|
Function | WE |
|
| Configuration | ||
Characteristic | OFF |
|
| FB19 = ON | ||
|
|
|
| |||
Parameters | WE | WE* | Range of values | |||
Outdoor temperature, point 1 | 20 °C | |||||
Outdoor temperature, point 2 |
|
| ||||
Outdoor temperature, point 3 | 5 | °C | 5 | °C |
|
|
Outdoor temperature, point 4 | 15 | °C | 15 | °C |
|
|
Flow temperature, point 1 | 70 °C | 50 °C | 20 to 130 °C | |||
Flow temperature, point 2 | 55 | °C | 40 | °C |
|
|
Flow temperature, point 3 | 40 | °C | 35 | °C |
|
|
Flow temperature, point 4 | 25 | °C | 20 | °C |
|
|
Return flow temperature, point 1 | 65 | °C | – |
| 20 to | 90 °C |
Return flow temperature, point 2 | 50 | °C | – |
|
|
|
Return flow temperature, point 3 | 35 | °C | – |
|
|
|
Return flow temperature, point 4 | 20 | °C | – |
|
|
|
20 | °C | 5 | °C | 0 to | 50 °C | |
Max. flow temperature | 90 | °C | 50 | °C | 20 to 130 °C |
42EB 5476 EN