Samson 5476 manual Start-up, Proceed as follows Switch to the parameter level

Models: 5476

1 114
Download 114 pages 58.6 Kb
Page 18
Image 18
Proceed as follows:

Start-up

Proceed as follows:

Switch to the parameter level.

Display shows: Time, Manual background blinks

Switch to the configuration level.

 

Display shows: Current system code number,

blink.

Select level displaying function blocks 0 to 23 or

Select level displaying function blocks 24 to 47.

Select function block.

Activate editing mode for function block. The function block number starts to blink.

If 0 0 0 0 0 appears on the display, the key number needs to be entered first. Refer to section 2.4

Activate function block (FB = ON).

An activated function block is indicated by a black square below (right) the function block number in the top row of the controller display.

or:

Deactivate function block (FB = OFF).

Confirm setting.

If the function block is not closed, further function block parameters can be adjusted. Proceed as follows:

Make the desired changes and confirm.

If applicable, the next function block parameter is displayed. Confirm all parameters to exit the opened function block.

To adjust additional function blocks within the configuration level, repeat the steps in the fields highlighted in gray.

Exit the configuration level.

Return to the operating level.

Note!

The controller automatically returns to the operating level if the keys are left unpressed for five minutes.

18EB 5476 EN

Page 18
Image 18
Samson 5476 manual Start-up, Proceed as follows Switch to the parameter level