Functions of the heating circuit
have been activated.
Refer to page 78 onwards for the wiring diagrams of the room panels.
Functions | WE | Configuration |
Room sensor RF | OFF | FB13 = ON |
Potentiometer input 1 to 2 kΩ | OFF | FB24 = OFF |
5.7Optimization
This function requires the use of a room sensor. Depending on the building characteristics, the controller determines and adapts the required preheating time (maximum 6 hours) to ensure that the desired Room set point (rated room temperature) has been reached in the reference room when the
Depending on the room sensor, the controller switches off the heating system up to two hours before the
During the preheating period, DHW heating does not take place in systems with DHW circuits linked in the secondary side.
Note!
Direct sunshine can cause the room temperature to increase and thus result in the premature de- activation of the heating system.
Function | WE | Configuration |
Optimization | OFF | FB0 = ON |
|
|
|
Parameter | WE | Range of values |
Room set point | 20 °C | 0 to 40 °C |
Reduced room set point | 17 °C | 0 to 40 °C |
Sustained temperature | 15 °C | 0 to 40 °C |
46EB 5476 EN