7.12 Setting a customized key number

System-wide functions

switches were set to “Night mode” or Heating circuit(s) deactivated” or “DHW heating un- changed”.

Function

WE

Configuration

Locking manual levels

OFF

FB34 = ON

7.12 Setting a customized key number

Switch to the parameter level.

Display shows: Time, Manual background blinks

Switch to the configuration level.

 

Display shows: Currently valid system code number,

blink

Select a function block (e.g. FB20) protected by the key number.

Open the function block.

0 0 0 0 0 appears on the display.

Set 01995 as the key number.

Confirm the key number.

Display shows: 00100

Enter current key number.

Confirm current key number.

Set new key number between 00100 and 01900.

Confirm new key number.

This new key number is now the active key number.

EB 5476 EN 63