Samson 5476 manual Appendix, Function

Models: 5476

1 114
Download 114 pages 58.6 Kb
Page 82
Image 82
Manual background

Appendix

FB

Function

WE

Anl

Comments

9

Parallel pump

OFF

2, 3,

FB9 = ON: Parallel pump operation

 

operation

 

9

Select (Anl 2 and 9):

 

 

 

 

PU: Parallel pump operation

 

 

 

 

US: Operation with switchover valve

 

 

 

 

Function block parameter (on selecting: US):

 

 

 

 

Stop parallel oper. in case of deviation / 2 to 10 min (10 min)

 

 

 

 

FB9 = OFF: Intermediate heating after 20 min

 

 

 

 

Select (FB9 = ON, US or FB9 = OFF):

 

 

 

 

20: Intermediate heating after 20 min

 

 

 

 

–: No intermediate heating

10

Control mode

ON

All

FB10 = ON: Three-step signal control mode

 

three-step RK1

 

 

Function block parameters:

 

 

 

 

KP (proportional gain) / 0,1 to 50 (0,5)

 

 

 

 

TN (reset time) / 1 to 999 s (200 s)

 

 

 

 

TY (valve transit time) / 15, 30, 45 to 240 s (90 s)

 

 

 

 

Pump lag time / 1 x TY to 10 x TY (2 x TY)

 

 

 

 

FB10 = OFF: On/off control; when FB10 = OFF also FB11 = OFF

 

 

 

 

Function block parameter:

 

 

 

 

Hysteresis / 1 to 30 °C (5 °C)

11

Limit deviation for

OFF

All

FB11 = ON, only when FB10 = ON: Limitation active

 

OPEN signal RK1

 

 

Function block parameter:

 

 

 

 

Max. deviation / 2 to 10 °C (2 °C)

12

Limit deviation for

OFF

4

FB12 = ON, only when FB17 = ON: Limitation active

 

OPEN signal RK2

 

to

Function block parameter:

 

 

 

11

Max. deviation / 2 to 10 °C (2 °C)

13

Room sensor RF

OFF

All

FB13 = ON: Sensor/remote operation activated

 

 

 

 

Cannot be selected when FB0, FB1 or FB2 = ON;

 

 

 

 

when FB0, FB1 and FB2 = OFF the room temperature is only

 

 

 

 

indicated and not used for the control

14

Storage tank sensor

ON

2, 3,

FB14 = ON: Sensor SF1 activated

 

SF1

 

5, 7,

Storage tank thermostat: FB14 = FB15 = OFF

 

 

 

8, 9,

 

 

 

 

11

 

15

Storage tank sensor

ON

2, 3,

FB15 = ON: Sensor SF2 activated

 

SF2

with

4, 5,

Select: --: Settings for plants with DHW heating in storage tank

 

 

3, 5,

7, 8,

charging system with 2 storage tank sensors

 

 

8,11

9,11

CF: Activated for solar circuit

 

 

 

 

Storage tank thermostat: FB14 = FB15 = OFF

82EB 5476 EN

Page 82
Image 82
Samson 5476 manual Appendix, Function