Communication
Note!
A 15 V DC supply voltage (+15 V at terminal 15 connected to the meter bus connection terminal
3)can be used at the WMZ connection of TROVIS 5476 Controller when the red jumper on the back of the controller is located pointing towards the edge of the controller (Fig. 8). Otherwise, the meter bus module in the heat meter is supplied. Furthermore, the heat meter is galvanically connected with controller input side (pulse and current input at terminal 15) resulting it being connected to the Modbus interface as well which can lead to the communication coming to a standstill.
9.4.1 Activating the meter bus
To successfully transfer data from the heat meter to the controller, the heat meter must use a standardized protocol in accordance with EN
A meter bus address must be unique and correspond with the address preset in the WMZ. If the preset meter bus address is unknown, a single heat meter connected to the controller can be as- signed the meter bus address 254. The address 255 deactivates the communication with the re- spective WMZ. The model code to be set for the heat meter can be found in
Function | WE | Configuration |
Meter bus | OFF | FB29 = ON |
| 254* | Meter bus address for WMZ 1 to 3 |
| 1434 | Model code WMZ 1 to 3 / 1434, CAL3, APAtO, SLS |
| Cont | Reading mode WMZ 1 to 3 / 24h, Cont, CoiL |
* WE for WMZ 2 and 3: 255
9.4.2 Flow rate and/or capacity limitation via meter bus
Similar to the flow rate limitation based on a standardized 0/4 to 20 mA signal, the update rate of the measured variable, flow rate and/or capacity, must be smaller than 5 seconds in meter bus operation to carry out a proper limitation. Refer to the technical documentation
EB 5476 EN 71