Samson 5476 manual Functions of the heating circuit, 5.1Weather-compensatedcontrol

Models: 5476

1 114
Download 114 pages 58.6 Kb
Page 40
Image 40
Functions of the heating circuit

Functions of the heating circuit

5 Functions of the heating circuit

Which controller functions are available depends on the selected system code number (Anl).

5.1Weather-compensated control

When weather-compensated control is used, the flow temperature is controlled according to the outdoor temperature. The heating characteristic in the controller defines the flow temperature set point as a function of the outdoor temperature (–> Fig. 2). The outdoor temperature required for weather-compensated control is measured at the outdoor sensor or received over a current input.

tVL Flow temperature

tA Outdoor temperature

Fig. 2 · Gradient characteristics

Measured at the outdoor sensor

Function

WE

Configuration

Outdoor temperature – Current input

OFF

FB18 = OFF

Received over (0)4 to 20 mA current input (a 50 Ω resistor must be connect to terminals 7(+) and GND (terminals ½) parallel to the current signal)

40EB 5476 EN