Appendix

FB

Function

WE

Anl

Comments

29

Meter bus

OFF

All

FB29 = ON: Meter bus communication activated

(5)

 

 

 

Function block parameters WMZ 1 to 3:

 

 

 

 

Meter bus address / 0 to 255 (WMZ1: 254; WMZ2, 3: 255)

 

 

 

 

Model code / 1434, CAL3, APAtO, SLS (1434)

 

 

 

 

Reading mode / 24h, Cont CoiL (Cont)

 

 

 

 

Setting only possible after entering key number!

30

Flow rate limitation

OFF

All

FB30 = ON: Flow rate limitation activated

(6)

 

 

 

Select: At: Outdoor temperature dependent limitation,

 

 

 

 

FB19 = ON when “At“ selected

 

 

 

 

---: Fixed limitation

 

 

 

 

Function block parameters:

 

 

 

 

Max. limit / 0.01 to 650 m3/h (2 m3/h)

 

 

 

 

Max. limit for heating* / 0.01 to 650 m3/h (2 m3/h)

 

 

 

 

Max. limit for DHW / 0.01 to 650 m3/h (2 m3/h)

 

 

 

 

Min. limit / 0.01 to 100 m3/h (---)

 

 

 

 

Limiting factor / 0.1 to 10 (1)

 

 

 

 

* Parameter does not need to be set when “At“ selected

 

 

 

 

Setting only possible after entering key number!

31

Capacity limitation

OFF

All

FB31 = ON: Capacity limitation activated

(7)

 

 

 

Select: At: Outdoor temperature dependent limitation,

 

 

 

 

FB19 = ON when “At“ selected

 

 

 

 

---: Fixed limitation

 

 

 

 

Function block parameters:

 

 

 

 

Max. limit / 0.1 to 6000 kW (15 kW)

 

 

 

 

Max. limit for heating* / 0.1 to 6000 kW (15 kW)

 

 

 

 

Max. limit for DHW / 0.1 to 6000 kW (15 kW)

 

 

 

 

Limiting factor / 0.1 to 10 (1)

 

 

 

 

* Parameter does not need to be set when “At“ selected

 

 

 

 

Setting only possible after entering key number!

32

Circulation over

OFF

5,

FB32 = ON: Control of DHW circuit remains released after

(8)

heat exchanger

 

11

storage tank charging

 

 

 

 

Setting only possible after entering key number!

33

Sensor calibration

ON

All

Cannot be deactivated

(9)

 

 

 

Setting only possible after entering key number!

34

Manual level

OFF

All

FB34 = ON: Locking activated

(10)

locking

 

 

Setting only possible after entering key number!

35

Lock dial-up

OFF

All

FB35 = ON: No dial-up in case of fault

(11)

 

 

 

Setting only possible after entering key number!

EB 5476 EN 85