Functions of the DHW circuit
DHW heating from the primary circuit (Anl 4):
The control valve opens depending on the DHW temperature from its closed position.
Stop storage tank charging
The controller stops charging the storage tank when the water temperature in the storage tank measured at sensor SF1 reaches the value T = DHW heating ON + Hysteresis. In systems with two storage tank sensors, the controller stops charging the storage tank when the water temper- ature in the storage tank measured at sensor SF2 reaches the value DHW heating OFF. In sys- tems with storage tank thermostat, the Hysteresis of the thermostat determines when the storage tank charging is finished.
When a high flow temperature is required by the system, the storage tank charging pump is im- mediately switched off. If no heating is taking place or if the flow temperature demand in the system is lower, the End charging process parameter applies for switching off the storage tank charging pump.
The storage tank charging pump is switched off at the latest after two transit time periods of the control valve (2 x TY).
Functions | WE | Configuration | |
Storage sensor SF1 | ON | FB14 | |
Storage sensor SF2 | OFF | FB15 | |
Return flow sensor RüF1 | ON | FB20 | |
|
|
| |
Parameters | WE | Range of values | |
DHW heating ON | 45 | °C | 20 to 90 °C |
DHW heating OFF | 50 | °C | 20 to 90 °C |
Hysteresis | 5 | °C | 0 to 30 °C |
Charging temperature | 55 | °C | 20 to 90 °C |
Stop charging | 53 | °C | 20 to 90 °C |
DHW temperature | 55 | °C | 20 to 90 °C |