Electrical connection
Connecting the sensors
Cables with a minimum
Connecting the actuators
Connect cables with at least 1.5 mm² suitable for damp locations to the terminals of the control- ler output. The direction of travel needs to be checked at
Set slide switch to (+). Valves must open. Set slide switch to
Connecting the pumps
Connect all cables with at least 1.5 mm² to the terminals of the controller as illustrated in the corre- sponding wiring diagram
Legend for wiring plans:
AF | Outdoor temperature sensor | SLP | Storage tank charging pump |
RF | Room temperature sensor | TLP | Heat exchanger charging pump |
VF | Flow temperature sensor | UP | Heating circulation pump |
SF | Storage tank sensor | ZP | DHW circulation pump |
RüF | Return flow temperature sensor | RK | Control circuit |
TWF | DHW sensor | BE | Binary input |
GND | Grounding of input signals | WMZ | Heat meter connection |
L + N | Mains supply | ZB | Meter bus interface |
CF | Solar circuit collector sensor | CP | Solar circuit pump |
Connections on the back of the controller, showing pump management as an example
Refer to the instructions of the pump manufacturer for further installation conditions.
EB 5476 EN 77