Functions of the DHW circuit
The amount of time in which the priority for the DHW circuit is given is set in the Priority in case of deviation parameter.
Function | WE | Configuration |
Priority for | OFF | FB8 = ON, Ab |
DHW circuit | 10 min | Priority in case of deviation / 2 to 10 min |
6.10 Forced charging of the DHW storage tank (Anl 2, 3, 5, 7, 8 and 9)
This function is always configured when the system has at least one storage tank sensor.
To provide the full room heating performance when the
6.11 Thermal disinfection of the DHW storage tank
In all systems with DHW heating, the DHW storage tank is thermally disinfected on a selected day of the week or every day. The storage tank is heated up to 70 °C. Thermal disinfection starts at 0.00h and finishes at 4.00h at the latest.
Thermal disinfection for preventing legionella infection causes
high return flow temperatures during the disinfection cycle (return flow temperature limita- tion suspended),
high storage temperatures after thermal disinfection has been concluded,
lime scale (possibly), which can have a negative effect on heat exchanger performance.
Note!
This function is not available when a storage tank thermostat is used.
Function | WE | Configuration |
Thermal disinfection | OFF | FB7 = ON |
| 3 (Mi) | Day of the week / |
56EB 5476 EN