Manual operation

Manual operation

3 Manual operation

Heating circuit and DHW circuit (Anl 9: underfloor heating circuit) can be set to manual mode at their operating mode selector switches.

Heating circuit mode selector switch

The heating circuit can only be set to manual mode when the DHW/underfloor heating circuit mode selector switch is not positioned at 3 Manual operation.

 

+

0

Anl 1, 2, 3

UP1 on, SLP/TLP off,

UP1 on, SLP/TLP off,

UP1 off, SLP/TLP off,

valve RK1 opens

valve RK1 stationary

valve RK1 closes

 

Anl 4, 5, 6, 11

UP1 on,

UP1 on,

UP1 on,

valve RK1 opens

valve RK1 stationary

valve RK1 closes

 

 

UP1 on,

UP1 on,

UP1 on,

Anl 7, 8

valve RK2 stationary,

valve RK2 stationary,

valve RK2 stationary,

 

valve RK1 opens

valve RK1 stationary

valve RK1 closes

 

UP1 on, SLP off,

UP1 on, SLP off,

UP1 on, SLP off,

Anl 9

valve RK2 stationary,

valve RK2 stationary,

valve RK2 stationary,

 

valve RK1 opens

valve RK1 stationary

valve RK1 closes

DHW circuit mode selector switch (system Anl 9: underfloor heating circuit)

 

+

0

Anl 2, 3

UP1 off, SLP/TLP on,

DHW heating inactive

DHW heating inactive

charging temp. control

 

 

 

 

 

Anl 4, 5, 6, 11

SLP/TLP on,

SLP/TLP on,

SLP/TLP on,

valve RK2 opens

valve RK2 stationary

valve RK2 closes

 

 

SLP/TLP on,

SLP/TLP on,

SLP/TLP on,

Anl 7, 8

valve RK1 stationary,

valve RK1 stationary,

valve RK1 stationary,

 

valve RK2 opens

valve RK2 stationary

valve RK2 closes

 

UP1 on, SLP on,

UP2 on, SLP off,

UP2 on, SLP off,

Anl 9

valve RK1 stationary,

valve RK1 stationary,

valve RK1 stationary,

 

valve RK2 opens

valve RK2 stationary

valve RK2 closes

 

 

 

 

Note!

In manual mode, frost protection is not guaranteed (–> section 7.2).