Manual operation
3 Manual operation
Heating circuit and DHW circuit (Anl 9: underfloor heating circuit) can be set to manual mode at their operating mode selector switches.
Heating circuit mode selector switch
The heating circuit can only be set to manual mode when the DHW/underfloor heating circuit mode selector switch is not positioned at .
| + | 0 | – | |
Anl 1, 2, 3 | UP1 on, SLP/TLP off, | UP1 on, SLP/TLP off, | UP1 off, SLP/TLP off, | |
valve RK1 opens | valve RK1 stationary | valve RK1 closes | ||
| ||||
Anl 4, 5, 6, 11 | UP1 on, | UP1 on, | UP1 on, | |
valve RK1 opens | valve RK1 stationary | valve RK1 closes | ||
| ||||
| UP1 on, | UP1 on, | UP1 on, | |
Anl 7, 8 | valve RK2 stationary, | valve RK2 stationary, | valve RK2 stationary, | |
| valve RK1 opens | valve RK1 stationary | valve RK1 closes | |
| UP1 on, SLP off, | UP1 on, SLP off, | UP1 on, SLP off, | |
Anl 9 | valve RK2 stationary, | valve RK2 stationary, | valve RK2 stationary, | |
| valve RK1 opens | valve RK1 stationary | valve RK1 closes |
DHW circuit mode selector switch (system Anl 9: underfloor heating circuit)
| + | 0 | – | |
Anl 2, 3 | UP1 off, SLP/TLP on, | DHW heating inactive | DHW heating inactive | |
charging temp. control |
|
| ||
|
|
| ||
Anl 4, 5, 6, 11 | SLP/TLP on, | SLP/TLP on, | SLP/TLP on, | |
valve RK2 opens | valve RK2 stationary | valve RK2 closes | ||
| ||||
| SLP/TLP on, | SLP/TLP on, | SLP/TLP on, | |
Anl 7, 8 | valve RK1 stationary, | valve RK1 stationary, | valve RK1 stationary, | |
| valve RK2 opens | valve RK2 stationary | valve RK2 closes | |
| UP1 on, SLP on, | UP2 on, SLP off, | UP2 on, SLP off, | |
Anl 9 | valve RK1 stationary, | valve RK1 stationary, | valve RK1 stationary, | |
| valve RK2 opens | valve RK2 stationary | valve RK2 closes | |
|
|
|
|
Note!
In manual mode, frost protection is not guaranteed
22EB 5476 EN