Appendix
12.3 Sensor resistance tables
Resistance values with PTC resistors
Type 5224 Outdoor Temperature Sensors, Type 5264 and Type 5265 Flow and Return Flow Temperature Sensors, Type 5264 Storage Tank Temperature Sensors
°C | 0 | 10 | 20 | 25 | 30 | 40 |
| 50 |
| 60 |
| 70 |
| 80 |
| 90 | 100 | 110 | 120 | |||||||||
Ω | 694 | 757 | 825 | 896 | 971 | 1010 | 1050 | 1132 | 1219 | 1309 | 1402 | 1500 | 1601 | 1706 | 1815 | 1925 | ||||||||||||
Type 5244 Room Sensor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
| °C |
| 10 |
| 15 |
| 20 |
| 25 |
| 30 |
|
|
|
| |||||||||||
Switch position | , terminals 1 and 2 |
| Ω | 679 |
| 699 |
| 720 |
| 741 |
| 762 |
|
|
|
|
Resistance values with Pt 100 resistors
Suitable Pt 100 sensors include
Outdoor temperature sensor: Type 5225
Flow and return flow temperature sensors: Type 5204, Type
Storage tank temperature sensor: Type 5205
Room temperature sensor: Type 5255
°C | 0 | 5 | 10 | |||||||
Ω | 86.25 | 88.22 | 90.19 | 92.16 | 94.12 | 96.09 | 98.04 | 100.00 | 101.95 | 103.90 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
°C | 15 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 |
Ω | 105.85 | 107.79 | 109.73 | 111.67 | 113.61 | 115.54 | 117.74 | 119.40 | 121.32 | 123.24 |
|
|
|
|
|
|
|
|
|
|
|
°C | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | 105 | 110 |
Ω | 125.16 | 127.07 | 128.98 | 130.89 | 132.80 | 134.70 | 136.6. | 138.50 | 140.39 | 142.29 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
°C | 115 | 120 | 125 | 130 | 135 | 140 | 145 | 150 |
|
|
Ω | 144.17 | 146.06 | 147.94 | 149.82 | 151.70 | 153.58 | 155.45 | 157.31 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Resistance values with Pt 1000 resistors
Use the resistance values listed in the table for Pt 100 resistors and multiply them by 10. Suitable Pt 1000 sensors include:
Outdoor temperature sensor: Type
Flow and return flow temperature sensors: Types 5207,
Storage tank temperature sensor: Types 5207,
Room temperature sensor: Type
98EB 5476 EN